Installation Sheet

3332
Figure 1
Screw
When installing a range hood insert, it is recommended to install the unit at a
minimum of 30˝ from the cooktop. For outdoor range hood inserts it is recommended
to install the unit at a minimum of 36˝ and a maximum of 42” from the grill top.
Use rigid ducting wherever possible. Try and minimize the use of elbows. It is
recommended to establish 15-20” of vertical airflow from the top of the hood
before executing a 90° turn or elbow. More elbows and longer runs create higher
static pressure. No more than two to three elbows are recommended. Use 40 feet
of ductwork max. The hood comes with a grounded three prong plug that can be
plugged into a 15 amp circuit.
1. Unpack contents of the hood. Attach transition piece and ducting to the top of
the range hood insert. Figure 1
2. Using L brackets and screws provided, attach L brackets to each side of the
insert.
3. Lift the range hood insert into cabinet or custom hood structure. Figure 2
4. Follow instructions for wall hood mount to mount the range hood.
NOTE: Due to some installation differences with custom hoods the L brackets may
not work. Before installing insert please determine if the insert will work for your
installation needs. You may pre-drill holes into the insert unit to accommodate for
custom hood installations.
Remote Blower Installation
Insert Installation
INSERT INSTALLATION
When installing your new remote blower type range hood, follow the instructions for
the type of hood you are installing. Remote blowers are available with wall, island,
under cabinet, and insert range hoods.
Make certain to connect the electrical cord to the hood and plug the blower motor in
to test the unit.
1. Run duct work into the area that you will install the remote from your range hood.
2. Fasten ducting to the range hood using a hose clamp and silver/duct tape.
3. Use the least amount of elbows as possible.
4. Mount the remote blower to studs only.
5. Run electrical cord (provided) back to the range hood.
6. Install a regular outlet with a 15 amp circuit.
7. The hood comes with a grounded 3 prong grounded plug. The cord is 26” long.
8. Run duct work to the outside of the house and add a back draft damper outside.
NOTE: The remote blower must be kept
inside the home, attic, or crawl space etc.
Never try to install a remote blower outside
of the home.
REMOTE BLOWER INSTALLATION
Screws
Screw
Figure 2 Figure 3
Screw