Installation instructions PF 6M-8M-11M-13M-15M Heat pump for swimming pool Réf. : N.C.003.B.EN - Ver.
1. Installation............................................................................................ 2 1.1 Generals ............................................................................................................. 2 1.1.1 Cautions ..................................................................................................................... 2 1.1.2 General terms of delivery ........................................................................................... 2 1.1.
1. Installation 1.1 Generals Carefully read this manual before installing, performing maintenance on or troubleshooting this device! The symbol indicates the presence of important information that must be taken into account to avoid injurying people or damaging the device. The symbol indicates the presence of useful information serving as a guideline. EN 1.1.
1.1.3 Storage and transport conditions The appliance must be transported upright on its pallet. EN 1.1.4 Field of application Exclusive use: heating swimming pool water It must not be used for anything else. 1.1.5 How it works Compressor Air 15 °C Air 10 °C Condenser Evaporator Water 28 °C Water 26 °C Expansion valve condenstates Temperatures for information 1.2 Technical characteristics PF Single phase voltage Power Power consumed* restored* kW 6.6 Nominale current COP* consumption* A 6.25 4.
1.3 Operating conditions Operating range: between 5 °C and 38 °C of air temperature between 5 °C and 32 °C of water temperature Maximum temperature limited at 32°C to protect the pool liner. 1.4 Installation EN Do not pick up the unit by the outside case, use the base to lift the unit. The installation and the hydraulic and electrical connections must be done to standards in force and especially standard NF C 15 100 for France (equivalent to EC I 364). 1.4.1 Access to technical compartment 1.4.
1.4.3 Installing the appliance installed the 5 anti-vibration studs (supplied, see §1.1.2), put onto a stable, solid (concrete slab type) and level surface, preserve from risks of flooding due to condensation produced by the appliance whilst it is operating (see §1.4.4) Fixing holes EN Possibility of fixing the appliance to the ground, using the holes in the base of the appliance. A diagram of drilling is available to the back of the packing box. 1.4.
V1-V2-V3: by-pass valves V5-V4: setting valves (optional) *minimum distance electrical protection boxes EN Condensation drainage: Caution: your appliance can drain several litres of water per day, and you are strongly advised to connect the drainage to the sewer. connect a Ø18 interior pipe (not supplied), to the grooved end piece mounted on the base of the appliance, outlet: to the back or on the side : 1.4.5 Electric connections 1.4.5.
acceptable tolerance of tension variation: ± 6% (while working), electric cables shall be fixed, use cable suited for outdoor use, of type RO2V or equivalent in countries outside the European Community, and with an outer diameter between 9 and 18 mm, use the stuffing box to bring the supply cable into the appliance 1.4.5.2 Connections Earth terminal green/yellow Fuse holder F1 3.
The minimum wire gauge for connection of the priority heating function is: 2x1.5 mm², of type RO2V or equivalent in countries outside the European Community, and with an outer diameter between 8 and 13 mm. Remove the plug (upper the cable gland) and fit the cable gland for passage of the cable into the unit. Once the cable is inserted in this stuffing box, block it by pulling lightly on the cable to retract it one centimeter.
1.5 Starting up 1.5.1 Presentation of the regulation : controller “on” indicator : priority heating output enabled indicator : “on/off” or stand-by : display required water temperature or setting : setting values : compressor “on” (steady) or timed (blinking) indicator : defrost in progress (steady) or timed (blinking) indicator 1.5.
If valves 4 and 5 are not present, open valve 2 completely and half close valve 3. switch on the electrical supply to the heat pump, When the regulator is first switched on, the following information messages appear: “REXX” then “MAPX”. if the heat pump is in stand-by: , press 3 seconds on seconds and then the water temperature is displayed.
retighten these connections one turn to avoid penetration of foreign bodies into the condenser, cover the heat pump with a micro-breathing overwintering cover (optional accessory, see §3.2). To avoid damaging the appliance with condensation, do not cover it hermetically. 2. Troubleshooting 2.1 Statuses and faults of the regulator 2.1.
Display (alternating with ) Designation Cause Solution Refrigerant circuit high pressure fault 1- emulsion of air and water passed in the appliance, 2- bad water flow, 3- exchanger fouled 4- flow controller jammed shut 1 - check the pool hydraulic circuit 2 - check the flow rate controler 3 - if the fault persists, contact an approved technician Sensor defective or disconnected (terminals 4-5 of the plate B1) Replace or reconnect the sensor Water flowrate sensor fault (ST4) Refrigerant circuit pr
2.2 Malfunctions of the appliance 2.2.1 The appliance does not work Causes Verification / solution No display Check the supply voltage and the fuse The pool temperature is above the temperature setpoint. Increase the temperature setpoint. A message is on the screen. Check the meaning of message §2.1 2.2.2 The appliance operates but the water temperature does not rise Causes Verification / solution Not enough filtering time Put the filtering on manual 24/24 hours to raise the temperature.
3. Maintenance 3.1 Maintenance instructions A general servicing of the appliance is recommended when wintering and restarting, to check the proper operation of your appliance, maintain its performance and to prevent some breakdowns. ensure no foreign bodies obstruct the fan grid, clean the evaporator with a soft brush and a fresh water jet, EN Do not use a high-pressure water jet.
3.3 Recycling the product Your appliance is reaching the end of its working life. You would like to get rid of it or replace it. Please do not throw it into the dustbin or into your local council’s selective sorting containers. When this symbol appears on a new appliance, it means that the equipment must not be thrown away and that it will be collected selectively so that it can be reused, recycled or recovered.
CONFORMITY CERTIFICATE Z.P.C.E. declares that the herewith products or ranges: Swimming pool Heat pumps: Power First 6M-8M-11M-13M-15M are in conformity with the provisions: of the ELECTROMAGNETIC COMPATIBILITY directive 2004/108/EC. of the LOW VOLTAGE directive 2006/95/EC. ADDITIONAL RECOMMENDATIONS In relation with the Pressurised Equipment Directive (PED-97/23/CE) 1.
Electric diagram PF 6M-8M * 1
PF 11M-13M-15M * 2
3 Flow rate controler Regulation sensor NTC Antifreeze sensor Defrost sensor NTC Water flow adjusting probe NTC Regulation electronic card J1 SD1 SD2 SD3 SD4 B1 Grey White Pink G Bl R Soft starter Soft starter Brown Compressor M2 M Fan M1 Blue Fan connector CX1 B Compressor capacitor C2 Black Fan capacitor C1 N Fuse 3.
Dimensions and description * English Base Front pannel cowl Technical door Back pannel Post Grid Regulator Ø1” ½ water pool inlet Ø1” ½ water pool outlet Evaporator Stuffing box B1 regulation electronic card Fuse F1 Supply terminal board 4