1.4.5 Electric connections
1.4.5.1 Voltage and protection
the electrical supply of the appliance must come from a protection and switching device (not
supplied) complying with the standards and regulations in force in the country (in France: NF C
15100).
an additional protection may be required during installation to guarantee the overvoltage category
II,
the unit is designed for connection to a general power supply with full earth and neutral or neutral
earth systems (in compliance with NF C 15-100),
electrical protection: by circuit-breaker (curve D) or fuse (Am) (for calibre, see §1.4.5.3), and with a
30 mA differential trip switch at the head of the supply line (circuit-breaker or switch),
Prior to any operation, check that the voltage on the identification plate of the
appliance corresponds to the mains voltage provided on site.
Condensation drainage:
Caution: your appliance can drain several litres of water per day, and you are
strongly advised to connect the drainage to the sewer.
connect a Ø18 interior pipe (not supplied), to the grooved end piece mounted on the
base of the appliance,
outlet: to the back or on the side :
V1-V2-V3: by-pass valves
V5-V4: setting valves (optional)
*minimum distance
electrical protection boxes