Unit installation

7
1.4.5.2 Connections
See placing § “dimensions and description” in the appendix
1.4.5.3 Cable sections
supply cable section: for cables of a maximum length of 20 metres (calculation base: 5A/mm²),
must be checked and adapted depending on installation conditions.
PF
Maximum current
consumption
Cable saction Electrical protection
A mm² A
6M
9 3 x 2.5 3G2.5 16
8M
10 3 x 2.5 3G2.5 16
11M
14.5 3 x 2.5 3G2.5 16
13M
16.1 3 x 4 3G4 20
15M
21.9 3 x 6 3G6 25
1.4.5.4 “Priority Heating” function
Objective: to keep the pool water at the required temperature, independent of the filtering time (the
heat pump triggers the operation of the filter every hour):
- the pool temperature > required temperature = the heat pump stops the filter system after 5
minutes.
- the pool temperature < required temperature = the heat pump switches on and keeps the filter
pump running until the correct temperature is attained.
Main advantages offered by this function:
- a guarantee that the heat pump operates long enough to attain the required temperature, in
particular during initial warm-up periods (no longer necessary to manually switch on the filter system
24h/24).
- constant control and monitoring of the pool heating requirements, even when the filter system has
been switched off by the timer.
Connection of the “priority heating” function: to use terminals 16 and 17 to come to control the pump of
filtration using the dry contact (I max. = 5 has
under 230Vac with circuit of class AC1 and I max. = 1,2A
under 230Vac with circuit of class AC3), see diagram hereafter.
The cable used for priority heating and the electrical power supply cable must be strapped
together inside the unit until just after the stuffing box.
The appliance must be earthed.
Risk of electrical shock inside the device. Only a qualified and experienced
technician can install the device’s cables.
If the power cable is damaged, it must be replaced by a qualified technician or in a
Zodiac Pool Care Europe technical station.
acceptable tolerance of tension variation: ± 6% (while working),
electric cables shall be fixed,
use cable suited for outdoor use, of type RO2V or equivalent in countries outside
the European Community, and with an outer diameter between 9 and 18 mm,
use the stuffing box to bring the supply cable into the appliance
Configuration of supply terminal rail
single-phase 230V-50Hz with phase (L)
+ neutral (N) + Earth
Fuse holder F1
3.15 A Type T
(timed) 250Vac
Earth terminal green/yellow