Install Instructions

© Copyright 2012 Zoeller Co. All rights reserved.
FOR YOUR PROTECTION ALWAYS DISCONNECT FROM POWER SOURCE BEFORE HANDLING. The “A-Pak” Alarm
system has a double insulated plastic enclosure for your protection and is supplied with a 2-prong plug.
SPECIFICATIONS
This alarm system monitors liquid levels in lift pump chambers, sump pump basins, holding tanks, sewage, agricultural
and other non-potable water applications. It features a red warning light, green “power on” light, alarm test switch and
horn silence switch. “A-Pak” primary voltage is 120 VAC, 60 Hz, 2.4 watts max (alarm condition) (circuit is not supervised).
Secondary voltage is 9 VDC (circuit is not supervised). Battery backup power is 9 VDC. NOTE: 9V battery is not included
and must be purchased separately.
NOTE: The alarm panel plugs into a standard household 120 VAC socket. DO NOT plug “A-Pak” Alarm System into the
same circuit as the pump. The “A-Pak” Alarm System should be connected to a circuit separate from the pump circuit.
Push test button to check alarm panel for operation.
ALARM PANEL INSTALLATION
1) Before installing alarm panel, remove battery cover on side of alarm panel and install a 9V battery. (not included)
2) Mount the alarm panel indoors with screws provided. NOTE: The mounting screw is to be located over a wall stud or
used with a wall anchor sized for a #8 x 1.25 self tapping screw.
3) Hang the panel by the keyhole in the back of the alarm enclosure and install the second screw between the tabs
located on bottom of the enclosure.
4) Using the provided cable clamp, secure the power cord to the outlet as shown (see Fig. A). Use existing receptacle
faceplate screw and supplied washer.
SECTION: 6.10.100
FM0483
0112
Supersedes
1111/2
PN 1012302 Rev. F
MODEL TAAB
Product information presented
here reects conditions at time
of publication. Consult factory
regarding discrepancies or
inconsistencies.
MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
visit our web site:
www.zoeller.com
®
Your Peace of Mind is Our Top Priority
®
NOTICE TO INSTALLER: Instructions must remain with installation.
Figure A
SK2148
“A-PAK” ALARM SYSTEM INSTALLATION INSTRUCTIONS
CONTROL SWITCH INSTALLATION
MECHANICAL FLOAT SWITCH
(10-1494, 10-2614)
1) Place cord into clamp and secure to discharge pipe as shown in clamp detail (see
Fig. B). NOTE: Do not install the cord under the hose clamp.
2) Tighten the hose clamp with a screwdriver. NOTE: Do not over tighten; over tightening
may cause damage to the plastic clamp.
3) Make sure the oat cable is not allowed to touch the excess hose clamp band during
operation.
4) The oat switch must be suspended seven inches below desired activation level. (see Fig. D)
5) Allow system to cycle to ensure proper operation.
FACEPLATE SCREW
WASHER
CABLE CLASP
3.5 INCH
TETHER LENGTH
FOR DOUBLE
FLOAT
3.5 INCH
MINIMUM
TETHER LENGTH
FOR PUMP
SWITCH
SK1301D
Figure B
CLAMP DETAIL
(Tether Length Non-Adjustable)
LIFT PUMP
Suspend control switch above pump turn on level. If a pump failure causes
high-level condition, the A-Pak Alarm System will activate (see Fig. C).
Figure C
SEWAGE HOLDING TANK
Suspend control switch into tank seven inches below desired
alarm level. A-Pak Alarm System will activate if oat ascends to
alarm level (see Fig. D).
SK1301b
Figure D
TEST
SILENCE
ALARM
POWER ON
ZOELLER
ALARM
ZOELLER
PUMP "ON"
PUMP "OFF"
FIBERGLASS
OR POLYETHYLENE
BASIN
"ON" LEVEL
VARIABLE LEVEL
CONTROL SWITCH
LEVEL
LEVEL
4" OF GRAVEL
ALARM
ZOELLER
TO POWER SUPPLY
TO POWER SUPPLY
UNICHECK
"DO NOT" PLUG "A-PAK ALARM SYSTEM
INTO THE SAME CIRCUIT AS THE PUMP
NOTE:
SK2376