Installation Guide

Testing Procedures
2
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
MODEL 975XL2 REDUCED PRESSURE PRINCIPLE
ASSEMBLY
Equipment Required: Differential pressure gauge test kit.
975XL2 TEST NO. 1
Purpose:
Test #2 check valve for tightness against reverse ow.
Requirement:
The valve must close tight against reverse ow under all pressure
differentials.
Procedure:
1. Attach the "HIGH" hose to test cock #2 and the "LOW" hose
to test cock #3.
2. Close #2 shut-off valve.
3. Open test cocks #2 and #3.
4. Open by-pass valves "C" and "A" and bleed to atmosphere
until all air is expelled.
5. Close by-pass valve "A". Open by-pass valve "B" and bleed
to atmosphere until all air is expelled. Close by-pass valves
"B" and "C".
6. Attach the "VENT" hose to test cock #4.
7. Slowly open by-pass valves "A" and "C" and keep by-pass
valve "B" closed.
8. Open test cock #4.
9. Indicated pressure differential will drop slightly. If pressure
differential does not continue to decrease, the #2 check valve
is considered tight.
975XL2 TEST NO. 2
Purpose:
Test #1 check valve for tightness and record pressure drop across
#1 check valve.
Requirement:
The static pressure drop across #1 check valve shall be greater than
the relief valve opening point (test #1), and at least 5.0 psid.
Procedure:
1. Close by-pass valve "A"
2. Close test cock #4, and disconnect "VENT" hose from test cock
#4.
3. Open by-pass valves "B" and "C" bleeding to atmosphere,
then close by-pass valve "B" restoring the system to normal
static condition.
4. Observe the pressure differential gauge and note this as the
#1 check valve psid.
975XL2 TEST NO. 3
Purpose:
To test operation of the differential relief valve.
Requirement:
The pressure differential relief valve must operate to maintain the
"ZONE" between the two check valves at least 2 PSID less than
the supply pressure.
Procedure:
1. Close by-pass valve "C" and open by-pass valve "A".
2. Open by-pass valve "B" very slowly until differential gauge
needle starts to drop. Hold the valve at this position and
observe the gauge reading at the moment the rst discharge
is noted from the relief valve. Record this as the opening
differential pressure of the relief valve.
#1 TEST COCK
#2 TEST COCK
#3 TEST COCK
#4 TEST COCK
#1 SHUT-OFF
VALVE
VENT HOSE
LOW SIDE HOSE
HIGH SIDE HOSE
BY-PASS
VALVE "B"
BY-PASS
VALVE "C"
BY-PASS
VALVE "A"
#2 SHUT-OFF VALVE
#1 CHECK VALVE
#2 CHECK VALVE
975 XL2
WILKINS
ZURN
175 PSI
180° F
ASSE 1013
VENT
www.zurn.com
®