Rated Flow (established by approval agencies)
Flow Characteristics
Zurn Industries, LLC | Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada | Zurn Industries Limited
7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, 877-892-5216
www.zurn.com
Typical Installation
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. Unless
otherwise specified, the assembly shall be mounted at a mini-
mum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and
maintenance. The installation shall be made so that no part of
the unit can be submerged.
OUTDOOR INSTALLATION
INDOOR INSTALLATION
Specications
The Reduced Pressure Principle Backflow Preventer shall be certified to NSF/ANSI/CAN 61, shall be ASSE® Listed 1013, rated to
180°F, and supplied with full port ball valves. The main body and access covers shall be low lead bronze (ASTM B 584), the seat
ring and all internal polymers shall be Noryl™ and the seat disc elastomers shall be silicone. The first and second checks shall be
accessible for maintenance without removing the relief valve or the entire device from the line. If installed indoors, the installation shall
be supplied with an air gap adapter. The Reduced Pressure Principle Backflow Preventer shall be a ZURN WILKINS Model 975XL2.
Capacity thru Schedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8" 1 1 2 3
1/4" 2 2 3 5
3/8" 3 4 6 9
1/2" 5 7 9 14
3/4" 8 12 17 25
1" 13 20 27 40
1 1/4" 23 35 47 70
1 1/2" 32 48 63 95
2" 52 78 105 167
AIR GAP
FITTING
12" MIN.
30" MAX.
FLOOR DRAIN
DIRECTION OF FLOW
FLOOR
975XL2
WILKINS
ZURN
12" MIN
30" MAX
PROTECTIVE
ENCLOSURE
OPTIONAL
WATER METER
INLET SHUT-OFF
AIR GAP
DRAIN
DIRECTION OF FLOW
OPTIONAL
LEAD-FREE STRAINER
(MODEL SXL)
975XL2
WILKINS
ZURN
WILKINS
XL
0
20
40
60
80
5
10
15
20
0
50
100
150
200
250
5
10
15
20
FLOW RATES (GPM)
PRESSURE LOSS (PSIG)
69
PRESSURE LOSS (kpa)
FLOW RATES (l/s)
MODEL 975XL2 3/4", 1", 1 1/4", 1 1/2" & 2" (STANDARD & METRIC)
35
3/4" (20mm)
1" (25mm)
1 1/4" (32mm)
2" (50mm)
103
15.8
12.6
9.56.3
3.2
5.0
3.82.52
1.26
1 1/2”
(40mm)
137
(PROVIDED BY OTHERS)