* Notes for Body Minimum Friction Loss Chart:
Minimum inlet pressure is 10 psi higher than set point or the additional body friction loss at intended flow, whichever is higher.
(friction loss may be important at flows above 20 ft/s)
Example: A 6” valve intended to flow 2000 GPM at 150 psi has a friction loss of 20 psi at 2000 GPM. The minimum inlet pres-
sure would be 150 + 20 = 170 psi. When inlet pressure is below set point, the outlet pressure will be the pressure at the inlet
minus the friction loss.
PRESSURE REDUCTION LIMIT
0
50
100
150
200
250
300
0 20 40 60 80 100 120
OUTLET PRESSURE (PSI)
INLET PRESSURE (PSI)
Safe
operating zone
Noise
zone
Damage Zone
Noise Limit
Cavitation damage
zone (intermittent
operation allowed)
Flow Characteristics
0
1
10
100
10 100 1000 10000
PRESSURE DROP (PSI)
FLOW (GPM)
BODY MINIMUM FRICTION LOSS
1-1/4" Globe & Angle
1-1/2" Angle
1-1/2" Globe
2" Globe
2" Angle
2-1/2" Globe
2-1/2" Angle
3" Angle
4" Globe & Angle
6" Angle
8" Angle
6" Globe
8" Globe
3" Globe
10" Angle
10" Globe
12" Globe
14" Globe
16" Globe
Job Name Contractor
Job Location Engineer