Model ZW209
Pressure Reducing Valve
Page 1 of 4
Zurn Industries, LLC | Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada | Zurn Industries Limited
7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, 877-892-5216
www.zurn.com
BODY CONFIGURATIONS GLOBE STYLE BODY
ANGLE
STYLE
BODY
END
CONNECTION
PRESSURE RATING
FULL
PORT
REDUCED
PORT
Threaded 400 psi max. 1 1/4"-3" n/a 1 1/4"-3"
Flanged
ANSI Class 150, 250 psi max.
1 1/2"-16" 3"-10" 1 1/2"-10"
ANSI Class 300, 400 psi max.
Grooved 300 psi max. 1 1/2"-10" n/a 1 1/2"-10"
MINIMUM INLET PRESSURE 10 PSI
TEMPERATURE RATING: Water 33°F to 140°F
PILOT SPRING RANGE: 15-150 psi
Standard Features
Epoxy Coated, FDA Approved
Pilot Assembly
“Wye” Type Strainer
Opening Speed Control (sizes 1 1/4" - 4")
Isolation Valves
Inlet and Outlet Pressure Gauges
ANSI Class 150 Flanges
Copper Tubing and Brass Fittings
Options (Add suffix letters to ZW209)
Function
C - 40XL2 Hydraulic Check with Isolation Valve
L - SC1 Closing Speed Control*
O - SC1 Opening Speed Control (Standard 1 1/4" -4")
Body
A - Angle Style Body
R - Reduced Port Body
Connections
G - IPS Grooved
TH - NPT Threaded
Y - ANSI Class 300 Flanges
Main Valve Options
V - Viton Rubber Internals, rated 180°F (1-1/4"-6",
only available with "LP" or "HP" Option)
Z - ZPI Visual Position Indicator
Pilot System
LP - 5-25 psi Low Pressure Range PV-PRD Pilot
(replaces PRXL)
HP - 30-300 psi High Pressure Range PV-PRD Pilot
(replaces PRXL)
SP - All Stainless Steel Pilotry (replaces all
brass fittings, pilot valve and copper tubing.
“GL” Option included)
SH - Stainless Steel Braided Hoses (only replaces
Copper Tubing)
RV - Pilot on Reverse Side
GL - Liquid Filled Gauge
SO - Limit Switch Open Trip
SC - Limit Switch Closed Trip
SD - Limit Switch Dual Trip
DIRECTION OF FLOW
Application
The Zurn Wilkins Model ZW209 Pilot Operated Pressure
Reducing Valve is designed for many applications where the
reduction of high inlet pressures to safe and stable outlet
pressure is required. The pilot assembly reacts to changes
in downstream pressure allowing the main valve to modulate
between the closed and open position ensuring a constant
downstream set pressure. Once the downstream pres-
sure reaches the pilot setting, the main valve will seal shut
preventing damage downstream. Pressure regulation is not
dependent upon flow rate, resulting in minimal pressure loss
through the valve. In addition the Model ZW209 comes stan-
dard with epoxy coating internally and externally for corrosion
protection, as well as isolation valves and pressures gauges
for quick and easy maintenance or repair.
Standards Compliance:
ANSI/AWWA C530
Meets the requirements of NSF/ANSI 61*
*(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)
Materials
Main Valve Body Ductile Iron ASTM A536
Main Valve Bonnet Ductile Iron ASTM A536
Disc Guide Stainless Steel
Seat Stainless Steel
Disc Buna-N Rubber
Diaphragm Nylon Reinforced Buna-N
Stem Stainless Steel
Spring Stainless Steel
*The closing speed control (optional) on this valve should
always be open at least three (3) turns off its seat.
Schematic Diagram
Item Description of Standard Features
1 Main Valve
2 850XL Isolation Valve
3 SXL "Wye" Type Strainer
4 Pressure Gauge
5 Restriction Fitting
6 PRXL Pressure Reducing Control

NSF/ANSI 61