Beckett GeniSys Lockout Alarm Module

52040U

Categories

Description

Overview: The GeniSys® 7505 Series Lockout Alarm functions as the interface between the primary control and an existing alarm panel or any alarm mechanism requiring contact closure in the event of a soft or hard lockout of the GeniSys® 7505 Series Oil Burner Control. Operation: When power is applied to the primary control, the alarm module continuously monitors the GeniSys control for both a hard and soft lockout signal. If the alarm module detects either a hard or soft lockout, normally open relay contacts on the module close, creating a short circuit between the output terminals. When the alarm module no longer senses a lockout signal or power is removed from the control, the module relay contacts will open. Specifications Maximum Alarm Module Contact Switching Current: 2 Amps (ac or dc) Minimum Alarm Module Contact Switching Current: 5 mA (ac or dc) Maximum Alarm Module Switching Voltage: 30V (ac or dc) Minimum Alarm Module Switching Voltage: 5V (ac or dc) Storage & Operating Ambient Temp: -40°F to +150...

Manuals

#TitleLanguagesPagesUpdated
1User GuideEN22022-03-27