GNB Industrial Power VRLA-AGM Battery 1140Ah 6 Volts

3-100G21

Categories

Description

GNB Industrial 1140Ah 6VDC VRLA Battery The Absolyte GP battery is of the valve-regulated lead-acid (VRLA) design and so can operate with lower maintenance (e.g. no maintenance water additions) in comparison to conventional flooded lead-acid batteries. The Absolyte GP VRLA design is also inherently safer than conventional flooded lead-acid batteries. Under normal operating conditions and use, the Absolyte GP battery minimizes hydrogen gas release, and virtually eliminates acid misting and acid leakage. Features & Specifications : Battery Voltage: 6 Volts DC Total Amp-hours @ 20 hour rate: 1140 Amp-hours Total Amp-hours @ 100 hour rate: 1300 Amp-hours Weight: 515 pounds Dimensions (L x W x H): 29.0" x 26.38" x 8.59" Electrolyte – 1.310 specific gravity acid (nominal) Safety vent – 3-10 psi opening pressure, self-resealing Terminals – Solid copper insert Positive plate – Patented lead calcium tin silver alloy Negative plate – Lead calcium grid alloy 20 years design life in float applications at 25°C (77°F) 1...

Manuals

#TitleLanguagesPagesUpdated
1GNB Absolyte GP Battery Module Data SheetEN122022-12-17
2GNB Absolyte Installation ManualEN322022-10-25
3GNB Absolyte OverviewEN42022-10-25
4GNB Absolyte RE SpecificationsEN122022-10-25