Honeywell 4 port Manual Pneumatic Switch w/ 3 position interchange
SP470A1018
Categories
Description
Pneumatic diverting switch used to manually divert, block, or bleed air in pneumatic air lines to revise control sequence with a change in conditions. Commonly applied on Day-Night, Summer-Winter, On-Off-Auto, or Start-Stop functions. Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell switches. Features Available in two-position or three-position devices. Mountable on a panel up to 7/16 in. (11 mm) thick. Complete with knob and scaleplate. Specifications Switch Type: Three Position Pneumatic Diverting Switch Switch Operation: Used to manually divert, block or bleed pneumatic air lines Airflow Usage: 0.175 scfm (82.6 mL/s) minimum at 1 psi pressure drop Air Connections: Barb fitting for 5/32 in. (4 mm) O.D. plastic tubing Maximum Safe Operating Pressure (psi): 30 psi Mounting: Panel mount Operating Humidity Range: 5 to 95% RH Temperature Range: 20 F to 140 F Dimensions: 1 5/8 in. high x 1 9/16 in. wide x 3 in. deep
Manuals
# | Title | Languages | Pages | Updated |
---|---|---|---|---|
1 | Install Instructions | EN,FR | 8 | 2022-03-24 |