Honeywell 3-port pneumatic manual or minimum position switch (10 psi span)

SP970A1005

Categories

Description

Used to manually position a remote damper actuator or to reset the setpoint of a pneumatic controller. They can also provide minimum damper position by setting a minimum pressure limit in the branch line to the damper actuator. Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell switches. Features Two spans available as shipped. Six spans with breakaway stops on knob. Pilot bleed and isolated pilot models available. Wall or panel mounting. Specifications Switch Type: Three-port pneumatic manual or minimum position switch Switch Operation: Used to manually position a remote damper actuator or reset setpoint of pneumatic controller Airflow Usage: 0.022 scfm (9.8 mL/s) Air Connections: Barb fitting for 5/32 in. (4 mm) O.D. plastic tubing Maximum Safe Operating Pressure (psi): 30 psi Mounting: Panel or wall Operating Humidity Range: 5 to 95% RH Output Span (psi): 10 psi (with 188 degree knob rotation), 13 psi (with 244 degree knob rotation), 16 psi (with 300 degre...

Manuals

#TitleLanguagesPagesUpdated
1Install InstructionsFR82022-03-22
2Submittal SheetN/A32022-03-22