Littelfuse Octal Plug-In Liquid Level Control, Fill Operation (120V)

LLC44B30A

Categories

Description

**Note:** Image may not be exact representation of item. LLC44B30A - LLC4 Series The LLC4 combines resistance sensing circuitry with solid-state timing to provide single probe level maintenance. On adjustable units, the sensitivity adjustment allows accurate level sensing while ignoring foaming agents and floating debris. Isolated 12VAC is provided at the probe to prevent electrolysis. A trickle current of less than 1mA determines the presence or absence of conductive liquid between the probe and common. The LLC4 Series can be used with many types of low voltage (resistance changing) transducers to perform other control functions like temperature limit control, photo limit control, condensation sensing, and ice sensing. Operation: Fill (Pump-Up Mode): When the liquid level falls below the probe, the time delay begins. This time delay prevents rapid cycling of the output relay and its load. At the end of the time delay, the output relay energize and remain energized until the liquid level rises and touches ...

Manuals

#TitleLanguagesPagesUpdated
1Product OverviewEN22022-03-24