MBS MBS KBR 32 150/1A 3VA Kl.3 Stromwandler Primary current:150 A Secondary current:1 A Line feed-through diameter:33 mm

32-0021

Categories

Description

The cable conversion converter finds his main area of use, subsequent installation, in order to avoid isolating the primary conductor. It is particularly suitable for installation in hard to reach places. By default, the delivery with 2.5m connection cable 2 x 0.75 mm² (color-coded: S1 = brown S2 = blue) Therm. Rated Continuous current: 1.2 x in Icth Therm. Nominal short-time current Ith: 60 x IN, 1 sec. Max. Operating voltage: 0.72 kV Insulation test voltage: 3 kV, ueff, 50 Hz, 1 Min. Nominal frequency 50 Hz Insulation class: E Applied Technical Standards: DIN EN 60044/1, VDE 0414 Part 1 This text is machine translated.

Manuals

#TitleLanguagesPagesUpdated
1Data SheetDE22020-01-11