MidNite Solar Circuit Breaker with Remote Trip
MNEDC125RT
Categories
Description
Circuit Breaker 125 Amp 125VDC Panel Mount with Remote Trip (Shunt Trip Circuit Breaker). MidNite's breakers are rated to break the full rated load at the rated voltage repeatedly, with NO DAMAGE. Always use a properly sized breaker for disconnecting. This breaker has the Remote Trip feature that allows it to work with our Battery Disconnect Module ( MNBDM-24 or MNBDM-48 ) and the Rapid Shutdown System. All MidNite circuit breakers can be used at 100% rated current when mounted in a MidNite enclosure. The remote trip voltage to be applied should be between 24 and 30 volts DC. The voltage applied must be a pulse lasting no more than 0.1 second or damage may result. There is no warranty on breakers with a burnt out trip coil. Features Breaker Torque Value: 30 In-Lbs (3.4NM) Environmental Rating - Type 1 (Indoor) AIC 10,000 at 125VDC Warranty - 5 yrs. Listed for US & Canada Specifications FL. AMP: 125 Max Volts: 150 Hertz: DC Delay: 14 Trip Amps: 156 Circuit: K0 V.Coil: 24(19TRIP)VDC Width is 1 inch (25.4mm) ...
Manuals
# | Title | Languages | Pages | Updated |
---|---|---|---|---|
1 | Breaker and Busbar Torque Specs | N/A | 1 | 2022-12-19 |
2 | Breaker and Busbar Torque Values | EN | 1 | 2022-12-02 |
3 | Breaker Time Delay Values | EN | 7 | 2022-12-19 |
4 | MidNiteSolarMNEDC125 E-Series Breaker Specifications | EN | 8 | 2022-12-02 |
5 | MidNiteSolarMNEDC125 Specifications | EN | 1 | 2022-12-02 |
6 | MNBirdhouse | N/A | 1 | 2022-12-19 |