Systemair DVG-H 800EC/F400 - Centrifugal roof fan, 400°C/2h, horizontal discharge
95255
Categories
Description
Roof unit for smoke and heat extraction + normal ventilation • Horizontal exhaust • Up to 400°C / 120 min (F400/120, F400/90, F300, F200) • Normal ventilation up to 120°C continuous operation, up to 80°C in standstill • Service switch serial • Suitable for coastal applications • Snow load class SL 1000 (suitable for heated or unheated buildings up to SL 1000) • Wide range of accessories • Tested acc. to EN 12101-3 at LGAI, Barcelona • CE-certified acc. to EN 12101-3 at BSI, UK • 1~ (sizes 355 and 450) or 3~ connection, 50/60 Hz • EC (electronically commutated) high efficiency motor inside • 0-10V speed control input • Modbus controllable • Fire mode DVG smoke and heat extract fans are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard ventilation. Smoke-free escape ways increase the chances to rescue people in case of fire. The casing is manufactured from seawater resistant aluminium. The base frame is made of pre-galvanized steel. Impeller with b...
Manuals
# | Title | Languages | Pages | Updated |
---|---|---|---|---|
1 | CERTIF DVV XS XL DVAX DVG BKF 2015 0086 CPR 597958 | EN | 6 | 2022-10-01 |
2 | DoP DVG | EN | 1 | 2022-10-01 |
3 | DVG EC E8301 19 01 2017 | EN | 12 | 2022-10-01 |
4 | IMO DVG | EN | 28 | 2022-10-01 |
5 | INSTRUCTION EC 3PHASE CONTROLLER 20 12 2016 V6 2 | EN | 21 | 2022-10-01 |
6 | Kitemark DVV DVG BKF MRH 646474 | EN | 7 | 2022-10-01 |