Systemair AXC 355 (F) - smoke extract axial fan 400°/2h

C355AXCF

Categories

Description

Smoke extract axial fan AXC(F) : ⁻ Certified according to EN 12101-3 for 400°C/120 min. ⁻ CE mark of conformity. ⁻ Suitable for use inside or outside the fire zone. Temperature of medium for continuous operation from -20°C up to 55°C. Air direction from motor to impeller. Impeller: ⁻ The adjustable blade angle allows flexible and exact adjustment to the desired working point with optimum efficiency. The blade angle is pre-set in the factory. ⁻ Impellers with profiled blades made of cast aluminum alloy. ⁻ Dynamically balanced according to ISO 21940-11 and ISO 14694, balancing quality G6,3. Casing: ⁻ Manufactured from hot-dip galvanized sheet steel according to ISO 1461. ⁻ Pre-drilled, rolled Eurovent 1/2 flanges pressed on both sides provide additional stability. ⁻ Pre-wired terminal box on fan casing for easy electrical connection, IP65 (IEC 60034-5). ⁻ PV version: Includes bolt-on outlet guide vanes which increases fan pressure and efficiency. Motor: ⁻ Motor suitable for 400°C/120min or 55°C continuous op...

Manuals

#TitleLanguagesPagesUpdated
1Company statemen FU AXCEN12022-09-30
2COMPANY STATEMENT FREQUENCY CONVERTER AXC(F)EN12022-09-30
3dop axc(f)009EN42022-09-30
4technical documentation manuals 308013008EN342022-09-30