The CDLSXX is a duct mount CO2 sensor that measures the levels of CO2 of air inside a duct. The CO2 sensor operates within accuracy specifications for an interval of 5 years and can be field calibrated. To maintain accuracy, all vents must remain clear and free of dust, debris, etc. Product Applications Controlling ventilation in response to occupancy ASHRAE 62.1 air quality standard compliance Office buildings, conference rooms, schools, retail stores, etc. Product Specifications Input Power: 20 to 30VDC/24VAC; 100mA max. Analog Output: 4-20mA (clipped & capped)/0-5VDC/0-10VDC (selectable) Operating Temp. Range: 0 to 50°C (32 to 122 °F) Operating Humidity Range: 0 to 95% RH non-condensing Housing Material: High impact ABS plastic < Output Range: 0 to 2000 ppm Accuracy: ±30 ppm ±2% of measured value Repeatability: ±20 ppm ±1% of measured value Response Time: <60 seconds for 90% step change Warranty: 5 years