Manual

0700015-J0 Rev B
70
6.7 Signals
This menu category consists of system identifiers and calibration controls. Parameters can be set/ac-
cessed such as controller signals, rectifier signals, analog and digital inputs. With the web interface, data
logging can be configured.
6.7.1 Calibrate Analog Inputs
This menu item provides a direct link to the Analog Inputs menu heading; which may also be accessed
via the menu item Configure Signals, see 6 .7. 2.
6.7.1.1 Overview of Analog Input Channels
The majority of the CXC analog input channels are each designed to accept a specific input signal.
2.1 summarizes the analog input channel assignments; which may vary depending on the hardware con-
figuration (list options):
= Installed
BiV = -60 V to +60 V
I = -50 mV to +50 mV
T = -55ºC to +100ºC (powered)
V = 0 to 60 V
X = Not Installed
Table E Analog input channel assignments
Channel List Option
CXCU
Assignment
120 121 122 123 124 125 129
V1 X
V2 X
GP1 T1 T1 T1 T1 V3 T1 T1 T1
GP2 T2 T2 T2 T2 V4 T2 T2 T2
GP3 X T3 X T3 V5 BiV T3 X
GP4 BiV T4 BiV T4 T1 BiV T4 X
I1
I2 X X X X X
I3 X X X X X X
I4 X X X X X X