Technical Specifications

ValVueFF Software Interface to FVP
176
GE Energy
This step requires permission level 3, 4, 8 or 9:
1. Open the Operation State dialog box.
2. Select Manual
3. Select OK.
4. Enter the Actual Position value, from step one, in the Set Point text box.
5. Select OK.
6. If the Failsafe dialog box changes to Clear (Latched), select the Clear Latch button.
7. Select OK when the dialog box request a change to OOS.
8. If the Failsafe dialog box remains in Active (Latched) proceed to Step Three.
Step Three
This step requires permission level 3, 4, 8 or 9:
1. Open the Configuration dialog box.
2. Select the Position tab.
3. Set the Tight Shutoff and Position Low Limit parameters to -10 lower than the Actual
Position value.
4. Set the Time 2 parameter to -1 (Figure 160).
Figure 160 Failsafe Step 1 and 2
5. Select OK to accept the changes.
6. Select Yes when a dialog box warns of a change to OOS state. The Failsafe dialog
box changes to Clear (Latched).