F3200 FIRE INDICATOR PANEL INSTALLATION & PROGRAMMING MANUAL F3200 PRODUCT MANUAL Document Number: LT0122 Issue .......... 2.7; 5 July 2001 -- A P P R O V A L S -AUSTRALIAN STANDARD AS1603.4 1987 (Incl.
F3200 Installation & Programming Manual Document No: LT0122 TYCO SERVICES FIRE & SAFETY END USER LIABILITY DISCLAIMER The F3200 Fire Indicator Panel has a configuration programming facility which may be accessed from the keypad by using a password. This programming facility allows the user to define detail of the operation of the F3200 System which is being customised. It is possible for the user to program operational features that prevent the installed FIP from meeting statutory requirements.
Document No: LT0122 F3200 Installation & Programming Manual TABLE OF CONTENTS End User Liability Disclaimer ................................................................................................... ii Amendments .......................................................................................................................... vi CHAPTER 1 INTRODUCTION............................................................................... 1-1 1.1 1.2 1.3 1.4 1.5 SCOPE ............................
F3200 Installation & Programming Manual 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 Document No: LT0122 AZC WIRING .........................................................................................................................8-10 MAF ANCILLARY RELAY WIRING .....................................................................................8-12 WARNING SYSTEM WIRING...............................................................................................8-15 MODULE RELAY WIRING .................
Document No: LT0122 F3200 Installation & Programming Manual AMENDMENTS ISSUE 1 DATE 20/04/94 2 30/01/95 2.1 01/02/96 2.2 16/04/96 2.3 01/12/97 2.4 09/04/98 2.5 22/03/99 2.6 14/06/00 2.7 05/07/01 Issue 2.7 COMMENTS Original. Corresponds to V1.10 software, which includes RZDUs, multiple access codes, revised print menu, NSW Coder, Programmable Alarm Text, Inst Alarm Text (not in V1.01) Was WP5.1. Upgraded for small FIP,6A PSU.
F3200 Installation & Programming Manual Document No: LT0122 THIS PAGE IS INTENTIONALLY LEFT BLANK Page vi 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Introduction CHAPTER 1 INTRODUCTION Issue 2.
F3200 Installation & Programming Manual Introduction 1.1 Document No: LT0122 SCOPE This manual provides information for the personnel responsible for planning, ordering, installing and programming an F3200 Fire Alarm System. It is assumed that such staff have been trained to plan/install fire alarm equipment and are familiar with the relevant standards. The manual is divided into the following chapters: Chapter 1 Introduction: Information on this manual.
Document No: LT0122 1.2 F3200 Installation & Programming Manual Introduction ASSOCIATED DOCUMENTATION 1.2.1 PRODUCT Additional information on the AS1603.4 approved F3200 FIP is found in the following product manuals. F3200 Operator's Manual A guide to the operation and maintenance of the F3200 FIP. Part Number LT0119 is a loose A4 version. Part Number LT0120 is a bound A5 version. F3200 Technical Manual A technical description of the F3200 system and modules. Part Number LT0121.
F3200 Installation & Programming Manual Introduction 1.3 Document No: LT0122 PRODUCT HISTORY LOG 1.3.1 HARDWARE Part No.
Document No: LT0122 F3200 Installation & Programming Manual Introduction SOFTWARE HISTORY LOG (CONTINUED) SF0164 SF0175 SF0178 F3200 Net EPROM NDU EPROM F3200 Std EPROM V2.06 V2.06 V2.06 Mar 1999 Mar 1999 Mar 1999 SF0229 SF0230 SF0231 F3200, Std Panel, c/w Tandem F3200, Networked, c/w Tandem NDU, c/w Tandem V2.07 V2.07 V2.07 May 2000 May 2000 May 2000 SF0229 SF0230 SF0231 F3200, Std Panel, c/w Tandem F3200, Networked, c/w Tandem NDU, c/w Tandem V2.08 V2.08 V2.
F3200 Installation & Programming Manual Introduction 1.
Document No: LT0122 F3200 Installation & Programming Manual Introduction GLOSSARY OF ABBREVIATIONS (CONTINUED) VA VB VNB +VBF +VNBF Z1 Zn1 8RM 8ZM : : : : : : : : : 1.
F3200 Installation & Programming Manual Introduction Document No: LT0122 THIS PAGE INTENTIONALLY LEFT BLANK Page 1-8 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual System Description CHAPTER 2 SYSTEM DESCRIPTION Issue 2.
F3200 Installation & Programming Manual System Description 2.1 Document No: LT0122 OVERVIEW 2.1.1 GENERAL The F3200 is a self-contained, modular, intelligent Fire Indicator Panel (FIP) which performs the functions of the Control and Indicating Equipment (CIE) as specified by the Australian Standard AS1603.4 Automatic Fire Detection and Alarm Systems. It is also available in formats that comply with AS4428.1. Refer to the relevant manuals that apply to the AS4428.1 approved products.
Document No: LT0122 F3200 Installation & Programming Manual System Description FIG 2.1.1 F3200, STANDARD CABINET - FRONT VIEW Issue 2.
F3200 Installation & Programming Manual System Description Document No: LT0122 FIG 2.1.2 F3200 OPERATOR DISPLAY PANEL Page 2-4 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual System Description FIG 2.1.3 F3200 - SMALL CABINET Issue 2.
F3200 Installation & Programming Manual System Description 2.1.4 Document No: LT0122 OUTPUTS The F3200 MAF/PSU Module provides 7 relays as standard. These are used for signalling to the Brigade (Fire Control Station) and for switching alarm bells and ancillary equipment such as door holders, airconditioning shutdown, etc. When more than 7 relays are required, additional sets of 8 can be added by fitting 8 Relay Modules.
Document No: LT0122 2.2 F3200 Installation & Programming Manual System Description PHYSICAL STRUCTURE The F3200 has a rugged, lockable painted steel cabinet, which houses 19 inch rack-mount equipment and comes in two height options (both have the same width and depth). The standard cabinet accommodates 15U total and the small cabinet accommodates 8U (where 1U = 1 3/4" = 44.5mm). The Operator Display has a screened, polyester overlay mounted on a hinged inner door fitted to the top 4U position.
F3200 Installation & Programming Manual System Description Document No: LT0122 Note: FP0551 and FP0713 have the cardframe as shown. FP0550 and FP0712 have the modules (3 max.) mounted on the rear wall. FIG 2.2.1 F3200 STANDARD CABINET - INTERNAL LAYOUT Page 2-8 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual System Description FIG 2.2.2 F3200, SMALL CABINET, MAXIMUM CONFIGURATIONS Issue 2.
F3200 Installation & Programming Manual System Description 2.3 2.3.1 Document No: LT0122 SYSTEM STRUCTURE PCB MODULES The 6 printed circuit boards which are used in an F3200 are as follows: Controller/Display Mounts on 4U inner door.
Document No: LT0122 F3200 Installation & Programming Manual System Description RS485 "Panel-Link" Network Board Connects to the Controller/Display Board Includes: RS485 Board used for connection to the Vigilant Network. FIG 2.3.1 SYSTEM STRUCTURE Issue 2.
F3200 Installation & Programming Manual System Description 2.3.2 Document No: LT0122 INTER-CONNECTION & STRUCTURE A basic F3200 system has one Controller/Display, one MAF/PSU, and one 8 Zone Module, all connected by Flat Ribbon Cable (FRC) on a common Input/Output (I/O) Bus. Additional 8 Zone Modules and/or 8 Relay Modules can be fitted to the I/O bus, with a maximum of eight 8 way modules. This is shown in the block diagram of Fig 2.3.1.
Document No: LT0122 F3200 Installation & Programming Manual System Description INTER-CONNECTION & STRUCTURE (CONTINUED) The relay LEDs simply follow the zone LEDs in the same order that they occur in the modules. E.g. a system with three 8 Zone Modules and two 8 Relay Modules would require 3 Display bds. Relay 1 would be annunciated on the 25th row of LEDs and the last 8 rows would be unused as shown in Fig 2.3.3. Mapping zones and relays to LEDs in other patterns is programmable. FIG 2.3.
F3200 Installation & Programming Manual System Description Zone 1 Module Relay 1 8 9 1 Display ........1 8ZM 8 Document No: LT0122 1 1 8 1 9 8ZM 16 8 17 1 8ZM 24 2 ........16 16 ........1 17 3 8 24 2 8RM 8RM 1 1 25 8 8....16 32 1 9....1 33 8 16.... 40 1 2 3 LAST 8 UNUSED 16 FIG 2.3.
Document No: LT0122 F3200 Installation & Programming Manual System Specifications CHAPTER 3 SYSTEM SPECIFICATIONS Issue 2.
F3200 Installation & Programming Manual System Specifications 3.1 GENERAL 3.1.1 FIP PART NUMBER & DESCRIPTION Document No: LT0122 Refer to Section 4 also. FP0550, F3200 FIP, NO CARDFRAME, 24 ZONE MAX, 1931-15 Includes: Full size cabinet (ie.
Document No: LT0122 3.1.3 F3200 Installation & Programming Manual System Specifications ENVIRONMENTAL Operating Temperature : -5°C to 45°C (Ambient) Relative Humidity : 95% maximum @ 40°C (non-condensing) 3.2 MECHANICAL SPECIFICATIONS CABINETS Style : Wall mounting Hinged outer door with large window (hinges to left) Accepts 19" rack mounting equipment 4U Display on hinged inner door (hinges to right) Construction : Welded steel Material : 1.2mm and 1.
F3200 Installation & Programming Manual System Specifications 3.3 3.3.1 ELECTRICAL SPECIFICATIONS MAINS SUPPLY Voltage Current Frequency Termination 3.3.2 Document No: LT0122 : : : : 240Vac +6% -10% 0.5A 50Hz For up to 2.5sq mm TPS 3 Way block with wire protectors BATTERY CHARGER & PSU Input Voltage (Transformer sec) : 31Vac rms Charger Voltage : 27.3Vdc (nominal at 20°C) Temperature Compensation : -36mV per °C nominal Non-Battery Backed : Voltage 28.
Document No: LT0122 F3200 Installation & Programming Manual System Specifications STATE MIN NOM MAX COMMENTS Charger High 28.05 28.125 28.20 Adjust with pot Charger Low 26.40 26.57 26.75 Battery Low 24.15 24.33 24.55 Standby Off 21.5 22.0 22.5 For voltage falling Notes: 1. All voltages stated in VDC at temperature of 20°C. 2. Apply temperature compensation of -36 mV/°C for temperature deviation from 20°C. 3. This applies also to charger voltage 27.3 VDC. 4.
F3200 Installation & Programming Manual System Specifications Document No: LT0122 3.3.5 CURRENT CONSUMPTION 3.3.5.
Document No: LT0122 3.3.5.2 F3200 Installation & Programming Manual System Specifications NDU Quiescent and Alarm Currents Slimline NDU (FP0714/FP0773/FP07744) Operating Voltage Termination : : Current Consumption : 24Vdc (18-28V) For up to 2.5sqmm TPS Quiescent 25mA Alarm 80mA Quiescent 70mA 85mA Alarm 165mA 150mA Full cabinet NDU (FP0715) Current Consumption (Aust mode)1 Current Consumption (NZ mode)2 1.
F3200 Installation & Programming Manual System Specifications 3.4 3.4.1 Document No: LT0122 INPUT SPECIFICATIONS AZC SPECIFICATIONS General Terminations On 8 Zone Module, 2 per AZC. Demountable screw terminal 1.5sq mm cable max. Number 8 AZCs per 8 Zone Module. 64 max per system.
Document No: LT0122 F3200 Installation & Programming Manual System Specifications AZC SPECIFICATIONS (CONTINUED) AZC current limit (note 1) Min Typ Max 13.5mA (14.5mA) 15.5mA 16.5mA EOL & detector quiescent 11.95mA EOL, no detectors 7.0mA (7.2mA) 7.8mA 8.2mA Fault threshold 4.4mA 5.75mA 6.8mA Detector quiescent 0mA 4.0mA Notes 1. The minimum figures shown are for battery voltage greater than the minimum Standby (Battery Fail) level i.e. 21.5V.
F3200 Installation & Programming Manual System Specifications Document No: LT0122 AZC SPECIFICATIONS (CONTINUED) Detector Alarm Currents The current available to a latched detector is the AZC supply current at the detector "Alarm" voltage minus the EOLR current and the remaining quiescent current at that voltage. The following graphs show current/voltage characteristics for the various modes of operation. GRAPH 3.4.
Document No: LT0122 F3200 Installation & Programming Manual System Specifications ICL+R = Current sourced through current limit and pull up resistor IAV = Current available to detectors with EOLR fitted IAV = ICL+R - IEOLR GRAPH 3.4.3 AZC CURRENT VS VOLTAGE MODE 2 (HIGH CURRENT) A short circuit at the end of an 800 Ohm line will give a B2 (Detector Operated) alarm. A short circuit at the end of a 2k Ohm line will give a B3 (programmable) condition. GRAPH 3.4.
F3200 Installation & Programming Manual System Specifications Document No: LT0122 AZC SPECIFICATIONS (CONTINUED) Timing Standard Delay (into Alarm, Fault, Normal) 2.3 sec (2.0 - 2.6 sec) AZC Reset 5.3 sec (5.0 - 5.6 sec) AZC Ignore Period 1 (after Reset) 2 sec nom (plus std 2.3 sec delay) AZC Ignore Period 2 (after Start Up or Programming) 1 sec nom (plus std 2.3 sec delay) AZC Time Into Alarm Programmable 0-250 sec AZC Time Out of Alarm Programmable 0-250 sec Refer to Section 7.2.
Document No: LT0122 F3200 Installation & Programming Manual System Specifications MAF/PSU INPUTS (CONTINUED) End of Line Resistor No. of Circuits 1 2 3 Supervision Current Circuit Resistance 0mA @ +5V, 1.5mA @ 0V, +ve to BELLS- terminal 100 Ohm max. 3.4.
F3200 Installation & Programming Manual System Specifications 3.5 Document No: LT0122 OUTPUT SPECIFICATIONS 3.5.1 8 ZONE MODULE OUTPUTS Type Darlington open collector Switch to 0V Voltage Rating 28.5V max, "off" state 1V max @ 30mA, "on" state 1.1V max at 100mA Current Rating 100mA max per O/P, 0.6A max per module 1A max per FIP. Transient Protection Allows external wiring Terminations 8 Way demountable screw terminal 1.5sq mm max.
Document No: LT0122 3.5.3 F3200 Installation & Programming Manual System Specifications MAF/PSU OUTPUTS Brigade Relays Number 4 Standby Normally energised De-energises on battery fail or panel fail Fault, Isolated, Alarm Normally de-energised Energise on active state Form 1 Pole changeover contacts Voltage-free Termination Demountable screw terminals 1.
F3200 Installation & Programming Manual System Specifications Document No: LT0122 MAF/PSU OUTPUTS (CONTINUED) Option 1 Pole changeover contacts Voltage-free Snip Links Lk2, 3, 4. Rating ELV only 30V, 2Adc resistive 30V, 1Adc inductive 24V, 1.5Adc inductive bells Operation Programmable Default Active on any unisolated zone alarm Supervision On Bells +, - only (ref 3.4.2) Power Supply Outputs 0Vdc Termination 1 non-demountable screw terminal 4sq mm max cable 2 demountable screw terminals 1.
Document No: LT0122 F3200 Installation & Programming Manual System Specifications MAF/PSU OUTPUTS (CONTINUED) Non-Battery Backed DC Supply Rating 28Vdc nom 2Adc, fused +VNBF Termination 1 non-demountable screw terminal 4sq mm max cable 1 demountable screw terminal 1.5sq mm max cable RZDU Comms Tx, Rx, 0V 3 Wire (+VBF2 also available) Transmission Rate 1200 Baud Protocol Vigilant F4000 Termination Demountable screw terminals 1.5sq mm max cable 3.5.
F3200 Installation & Programming Manual System Specifications Document No: LT0122 CONTROLLER/DISPLAY (CONTINUED) Pin 2 3 5 1 4 6 7 8 Tx Rx 0V └──┴──┘ └──┘ 25 Way Miniature D available via transition cable Part Number LM0042 Female Pins (socket) Pin 2 3 7 6 8 20 Rx Tx 0V └──┴──┘ Alternative Function (on same serial port) Serial Port 0 10 Way FRC header, J2 UART signals: RXD, TXD, RTS-, CTS-, DCD5V levels; 0V, +5V, +24V also available Network 1 10 Way FRC header, J7 (fitted only for network systems) N
Document No: LT0122 3.
F3200 Installation & Programming Manual System Specifications 3.7 Document No: LT0122 DISPLAYS Standard Display Includes Panel Size FFCIF Type Standard LCD Size : : : : : Site Name Zone Name Relay Name FFCIF LEDs System Status LEDs : : : : Internal Status LEDs : : LCD; FFCIF LEDs; System Status LEDs 19", 4U 3 (common indicators & common controls) Complies with AS4050 (int) - 1992 2 Lines of 40 characters 5.5mm (H) x 3.2mm (W) per character 40 Characters max. 30 Characters max. 30 Characters max.
Document No: LT0122 F3200 Installation & Programming Manual Ordering Information CHAPTER 4 ORDERING INFORMATION Issue 2.
F3200 Installation & Programming Manual Ordering Information 4.1 Document No: LT0122 ORDERING INFORMATION The following lists the part numbers for the range of products and spares associated with the AS1603.4 approved F3200. It includes a brief description where considered necessary. FA1227,FAB,1931-24,F3200 BLANK PANEL,PLASTIC,9.
Document No: LT0122 F3200 Installation & Programming Manual Ordering Information ORDERING INFORMATION (CONTINUED) FP0712,FP,F3200 FIP,NO CARDFRAME,24 ZONE MAX,6A PSU FP0713,FP,F3200,FIP,64 ZONE MAX,6A PSU FP0714,FP,NETWORK DISPLAY UNIT (NDU),SLIMLINE,WALL MOUNT FP0715,FP,NETWORK DISPLAY UNIT (NDU),FULL CAB & MAF/PSU FP0731,FP,RDU TO NDU UPGRADE KIT FP0733,FP,NETWORK DISPLAY UNIT,4U 19" RACK MTG,NO MAF/PSU FP0749,FP,F3200 6A PSU UPGRADE KIT,1931-44 Kit to purchase to upgrade on existing panel to a 6A PSU.
F3200 Installation & Programming Manual Ordering Information Document No: LT0122 ORDERING INFORMATION (CONTINUED) LM0042,LOOM,1888-62,PROG PORT TO 25 PIN SERIAL (cable to connect printer/computer to Controller, has 25 pin min D) LM0044,LOOM,1901-81-1,DISPLAY EXTENDER FRC,2M LM0045,LOOM,1901-81-2,DISPLAY EXTENDER FRC,5M LM0046,LOOM,1901-81-3,DISPLAY EXTENDER FRC,0.5M LM0049,LOOM,1901-81-4,DISPLAY EXTENDER FRC,0.
Document No: LT0122 F3200 Installation & Programming Manual Ordering Information ORDERING INFORMATION (CONTINUED) ME0069,MECH ASSY,1931-57,1 ZONE, 1U GAS CONTROL PANEL (similar to ME0065 except on a non-hinged, 1U panel) ME0072,MECH ASSY,1931-70,F3200 RACK MTG GEARPLATE (allows F3200 internals to be fitted to a RAC cabinet. Factory fit option only. See Note 1) ME0155,MECH ASSY,694-384,19" 4U CFA ASSEMBLY ME0250,MECH ASSY,1919-35,RAC CABINET,IP65,20U X 200 (ie.
F3200 Installation & Programming Manual Ordering Information Document No: LT0122 ORDERING INFORMATION (CONTINUED) NEW ZEALAND OPERATION ONLY A variety of display options are available to satisfy varying NZ requirements. These are covered in detail in Section 12.8. Ordering codes are included for the various components for each option. Major items are as follows: PA0499 PCB ASSY, NZ DISPLAY EXTENDER BOARD NZ Display Extender Board in standard 16 Zone LED board format.
Document No: LT0122 F3200 Installation & Programming Manual Configuring a FIP CHAPTER 5 CONFIGURING A FIP Issue 2.
F3200 Installation & Programming Manual Configuring a FIP 5.1 Document No: LT0122 GENERAL An F3200 FIP is configured to suit a particular customer's requirements by: Fitting and connecting the required pcb modules; adding appropriate battery test resistors when necessary; adjusting or removing links on the pcbs; programming the FIP. The detectors, manual call points (MCPs), warning devices, ancillary equipment and field wiring that are connected to the FIP must match the FIP configuration.
Document No: LT0122 5.3 F3200 Installation & Programming Manual Configuring a FIP BATTERY & POWER SUPPLY 5.3.1 GENERAL The F3200 FIP has a dc power supply, which also serves as battery charger and requires a 24V sealed lead acid battery (i.e. 2 x 12V batteries in series) to be fitted. (See Section 3.3.3 for compatible batteries). Battery leads with 4.8mm Quick Connect receptacles (for connecting to the battery tabs) are included. Charger Rating (Refer to AS1670.1 Section 8.
F3200 Installation & Programming Manual Configuring a FIP Document No: LT0122 GENERAL (CONTINUED) 4. The approvals laboratory recommends using 90% derating of batteries used on F3200 because the battery fail voltage (Standby) is 22V instead of 21V (as used on some other FIPs).
Document No: LT0122 5.3.3 F3200 Installation & Programming Manual Configuring a FIP EXAMPLE BATTERY/CHARGER CALCULATIONS An example FP0551 FIP has the following configuration: 3 8ZMs total (i.e. 2 x FP0553 expansion modules fitted) 1 8RM fitted 20 AZCs enabled, 4 disabled 42mA total detector current on the 20 AZCs 350mA of door holders off +VNBF 5 relays on the 8RM used, with supervision enabled, all switching 24V, 50mA relays, normally de-energised.
F3200 Installation & Programming Manual Configuring a FIP Document No: LT0122 Suggest that two 12V, 10 Ahr sealed batteries from list in Section 3.3.3. would be adequate (or next size up, e.g. 17 Ahrs). Note that these require a 68E, 10W battery test resistor to be fitted to the tabs on the MAF/PSU as described in Section 5.3.5. 5.3.4 BATTERY SIZE The maximum battery size given in the specification, Section 3.3.
Document No: LT0122 5.3.5 F3200 Installation & Programming Manual Configuring a FIP BATTERY TEST RESISTORS The standard battery test resistor is suitable for a battery of capacity of up to 6.5AHr. For larger batteries, additional resistors must be fitted, either directly to the MAF/PSU pcb (in R34 and/or between Battery Test tabs), or within the FIP and wired to the Battery test tabs. Where the additional resistors are carrying a current of greater than 0.
F3200 Installation & Programming Manual Configuring a FIP Document No: LT0122 A. FOR ADDITIONAL TEST LOAD GREATER THAN 0.7A AND ALARM LOAD/CHARGER CURRENT LESS THAN 3A. B. FOR ALARM LOAD/CHARGER CURRENT GREATER THAN 3A. FIG 5.3.1 CONNECTION OF BATTERY TEST RELAY/RESISTOR Page 5-8 5 July 2001 Issue 2.
Document No: LT0122 5.3.6 F3200 Installation & Programming Manual Configuring a FIP BATTERY OVERCURRENT PROTECTION The MAF/PSU has two parallel PTCs, rated to carry over 3A, for battery overcurrent protection. Where the Alarm load from the battery to FIP is greater than 3A (i.e. with mains failed), or where a 6A power supply is used, an external, self-resetting, overcurrent device of suitable rating (greater than 6A, less than 35A e.g.
F3200 Installation & Programming Manual Configuring a FIP Document No: LT0122 POWERING AN F3200 FROM AN EXTERNAL DC SUPPLY (CONTINUED) Without a mains connection, F3200 will indicate “Mains Fail” in a system fault recall but this is not actually a fault and can be ignored. WIRING Disconnect the secondary wires of the transformer from the AC IN tabs on the MAF/PSU. Cable tie them safely out of the way (if the mains is not connected they will not be live).
Document No: LT0122 5.4 5.4.1 F3200 Installation & Programming Manual Configuring a FIP LINKS ON PCB MODULES CONTROLLER/DISPLAY Apart from E2INIT (SW1) and DATABASE WRITE PROTECT/ENABLE (Lk7) all links on the Controller Display are factory set. (These configure the pcb for memory chips used, other functions, and type e.g. as a FIP Controller or an RZDU Controller). SW1 and Lk7 are described in Section 6.3.1. 5.4.
F3200 Installation & Programming Manual Configuring a FIP 5.5 Document No: LT0122 ERROR MESSAGES DURING FIP CONFIGURATION Listed below are some error messages that can appear on the LCD during installation. Refer also to Section 6.6.3 System Faults in the Operator Manual LT0119. Error messages that can occur on startup or exit from program mode "Shift reg clocking fault" "Invalid # shift regs.
Document No: LT0122 F3200 Installation & Programming Manual Programming CHAPTER 6 PROGRAMMING Issue 2.
F3200 Installation & Programming Manual Programming 6.1 Document No: LT0122 INTRODUCTION 6.1.1 GENERAL The F3200 has two main levels of programming. The first level is accessible to the Operator (via the keypad) and does not require entry of an access code. It allows the setting of parameters, such as time and date, which do not affect the basic structure of the system. The second level allows entering of data into the database to configure the operation of the FIP.
Document No: LT0122 F3200 Installation & Programming Manual Programming GENERAL (CONTINUED) If "CLEAR ESC" is pressed enough times, the programming mode display is exited and the database checksum is calculated. BASE DISPLAY PRESS “SET” KEY TO ENTER FIG 6.1.1 MENU STRUCTURE Details of the programming menu are shown in Figures 6.1.2A-C. Figure 6.1.2A is for V1.00 and V1.01 software Figure 6.1.2B is for V1.10 software Figure 6.1.2C is for V2.
F3200 Installation & Programming Manual Programming Document No: LT0122 THIS PAGE LEFT INTENTIONALLY BLANK Page 6-4 5 July 2001 Issue 2.
F3200 Installation & Programming Manual Programming 6.1.3 Document No: LT0122 PROGRAMMING KEYS Looking at the keypad (or picture in Fig 2.1.2) the user will observe a 4x4 "numeric" keypad, and a row of function keys across the bottom. The function keys from "RECALL" to "BELLS ISOL" all have two functions e.g. "BELLS ISOL/DELETE". In programming mode, these keys operate the bottom functions i.e. "DELETE", "INSERT", etc.
Document No: LT0122 6.1.5 10 F3200 Installation & Programming Manual Programming RECOMMENDED PROCEDURE FOR CONFIGURATION & PROGRAMMING (CONTINUED) Checking When all parameters are entered, either: 1. Print the database (as per Section 6.3.4) and compare the printout against the configuration sheets (check each parameter for each item and tick off). or 2. If a printer is not available, de-access the database as per Section 6.3.
F3200 Installation & Programming Manual Programming 6.2 Document No: LT0122 SET MENU & OPERATOR PROGRAMMING FUNCTIONS 6.2.1 GENERAL From the base display, pressing the "SET" key enters the programming menu as shown in Fig 6.1.2. This gives the Operator programming options as follows: 1 Set Time; 2 Set Date; 3 View Data; 4 Program Data; 5 Bds Present; 6 More Operator Accessible Options Options 1,2 and 5 are Operator accessible and do not affect the database.
Document No: LT0122 6.3 F3200 Installation & Programming Manual Programming INITIALISING, ACCESSING, DE-ACCESSING, PRINTING, SAVING, LOADING & VERIFYING THE DATABASE 6.3.1 INITIALISING THE DATABASE The E2 INIT (initialisation) sequence causes the FIP to accept the module configuration found and store this in its database. Note that this also sets all other parameters to the default option and erases all other programmable data in the database e.g. zone names, output logic equations.
F3200 Installation & Programming Manual Programming Document No: LT0122 ACCESSING THE DATABASE (CONTINUED) WARNINGS 1. When the database is accessed the Controller de-energises the Standby relay (i.e. transmits Standby) and stops processing. If this signals "Alarm" to the Brigade the appropriate arrangements should be made. 2. On a FIP that has been commissioned, if there is concern that changes made to the database (e.g.
Document No: LT0122 F3200 Installation & Programming Manual Programming PRINTING & SAVING THE DATABASE (CONTINUED) To print or save the database, use the PRINT key from the base display (i.e. press CLEAR/ESC repeatedly until the base display is showing then press PRINT) and select option 3 to print the database or option 5 to save the database, then enter the access code. To print just the output logic part of the database, select option 4.
F3200 Installation & Programming Manual Programming Document No: LT0122 RESTORING THE DATABASE FROM A COMPUTER (CONTINUED) Note: The FIP will transmit XON, XOFF characters for handshaking if it needs to slow down the rate of data being sent to it. So, where possible, the computer should be set up for XON XOFF handshaking. If XON/XOFF handshaking is not available, or if errors occur, then a slower baud rate (2400) should be used. 6.3.
Document No: LT0122 6.4 F3200 Installation & Programming Manual Programming PROGRAM DATA MENU, TEXT & GLOBAL PARAMETERS 6.4.1 GENERAL The Program Data menu (refer to Fig 6.1.2) allows the user to program the following options: 1:Access Codes; 2:Text; 3:Global Data; 4:System Configuration; and 5:DBload. Option 5:DBload is described in Section 6.3.5, and System Configuration is described in Chapter 7. Option 3:Global Data is described in Section 6.4.4.
F3200 Installation & Programming Manual Programming 6.4.3 Document No: LT0122 TEXT ENTRY The Text option allows entry of the following: 1. 2. 3. 4. 5. 6. 7. a 40 character name for the site a 30 character name for each zone a 30 character name for each module relay a 30 character name for each ancillary relay a 6 character name for each of the 9 programmable alarm text messages. a 40 character fault action text. a 12 character Tandem LCD password.
Document No: LT0122 F3200 Installation & Programming Manual Programming PROGRAMMING TEXT WITH THE KEYPAD (CONTINUED) Example of Entry of Site Name Enter the site name "Penrose No 1 Store". From the Text Entry menu select option 1, Site. The LCD has the inactive cursor in the first position of the top field and the active cursor on A in the bottom field. Move the cursor right with the " key until the letter P is selected. Press "ENTER". The letter P should appear in the top field.
F3200 Installation & Programming Manual Programming 6.4.3.2 Document No: LT0122 TEXT PROGRAMMING WITH A PC F3200 allows the text names for zones, relays, etc, to be entered from a PC using the F3200 printer port. F3200 software V1.00 does not support this feature at all. Software V1.10 and V2.00 support all the commands with the exception of the fault action text (F command). Software V2.01 onwards adds support for the F command.
Document No: LT0122 F3200 Installation & Programming Manual Programming TEXT PROGRAMMING WITH A PC (CONTINUED) The DELETE or BACKSPACE keys may be used to delete the last character typed, and the ESCAPE key may be used to abort the text entry for the selected item. After the ENTER key is pressed the message "Saved OK" will appear if the text has been saved correctly into EEPROM. To load a file of text names from the PC into the F3200 panel, the file should be set up as shown in the following example.
F3200 Installation & Programming Manual Programming Document No: LT0122 TEXT PROGRAMMING WITH A PC (CONTINUED) I0 JEH I1 MJS . . I9 BAC F Phone VIGILANT FIRE 7903600 (three characters) (40 characters max) To initiate the loading of the file into the F3200 panel, enable remote text entry as described above. Run a terminal emulation program on the PC and press ENTER on the PC.
Document No: LT0122 F3200 Installation & Programming Manual Programming GLOBAL DATA (CONTINUED) For V2.
F3200 Installation & Programming Manual Programming Document No: LT0122 GLOBAL DATA (CONTINUED) FFCIF options The parameters which can be programmed to configure the FFCIF operation are: FFCIF type The default type of FFCIF operation is, 3 where an alarm is automatically displayed on the LCD and alarms must be individually acknowledged. Where LED displays are fitted for each zone and the automatic display with individual acknowledgement is not required, type 2 may alternatively be selected.
Document No: LT0122 F3200 Installation & Programming Manual Programming GLOBAL DATA (CONTINUED) Cause Preview, Alarm Type, Acknowledge State, Number of Alarms. and when the "AND." key is pressed, the first line changes to: Full Cause, Alarm Time, Number of Alarms. The Cause Preview consists of the first section of the Full Cause. Note: This setting affects ALL events, network or local, shown on the local F3200. It does not affect the format of information sent to other F3200s on a network, or to RDUs.
F3200 Installation & Programming Manual Programming Document No: LT0122 GLOBAL DATA (CONTINUED) Country Coder (alarm signalling) This is only required for FIPs connected to Brigades with NSW Country Coder equipment. It allows the selection of a code of 1 to 6 pulses to be signalled on the FIP Brigade Alarm relay. These occur in a repeated sequence of 3 seconds off followed by 1 second on for each pulse, with a space of 1 second between pulses.
Document No: LT0122 F3200 Installation & Programming Manual Programming GLOBAL DATA (CONTINUED) Daylight saving start/end This allows the selection of a date and time and a time difference for the start and end of daylight saving to allow the panel to automatically set the time forward or back. The programming of the start and end is identical and is described jointly here.
F3200 Installation & Programming Manual Programming Document No: LT0122 GLOBAL DATA (CONTINUED) The following table indicates suitable settings: COUNTRY/STATE FORWARD ENABLE D MONTH SUNDA Y BACKWARD HOUR MONTH SUNDA Y HOUR NSW, ACT, VIC, SA Y 10 L 2 3 L 3 TAS (1) Y 10 L 2 3 L 3 NZ Y 10 1 2 3 3 2 WA, NT, QLD (2) N - - - - - - NOTE: (1) (2) Tasmania may start Daylight Saving earlier at their discretion. WA, NT and QLD do not have Daylight Saving.
Document No: LT0122 F3200 Installation & Programming Manual Programming GLOBAL DATA (CONTINUED) V2.07 or later software • Enablement of Keys in 4 Operating States V2.07 or later software allows each keyboard key to be enabled or disabled in each of 4 operating states. This allows the keyboard functionality to be configured for each different installation. It is recommended that the key enablement feature in V2.07 not be used (upgrade to V2.08 or higher).
F3200 Installation & Programming Manual Programming Document No: LT0122 GLOBAL DATA (CONTINUED) Remote Sounder Silence This option is available in V2.07 or later software. Selecting this option shows a menu of: 1:sysflt reset [Y/N] 2:ffcif actions [Y/N] 3:all commands [Y/N] These options determine whether a remote networked panel or RDU can silence the buzzer at this panel. If “sysflt reset” is set to “Y” the buzzer is turned off when a Reset System Faults command is received from a remote panel.
Document No: LT0122 F3200 Installation & Programming Manual Programming GLOBAL DATA (CONTINUED) The parameter “Fault sounder after 8 hrs isolate” enables the fault buzzer to be activated if an isolate state (zone or relay) has been present for 8 hours with no operator intervention. The AS4428.1 Standard requires this to be enabled. New Zealand Mode This option is available with V2.08 or later software and only for an NDU (not for F3200).
F3200 Installation & Programming Manual Programming Document No: LT0122 The following table lists all of the programmable non-network parameters. The defaults listed are for Australian operation. The previous section lists items that have defaults specific to New Zealand operation.
Document No: LT0122 F3200 Installation & Programming Manual Programming Item Bells Isol Key (V2.06 or earlier) Ancil Isol Key (V2.
F3200 Installation & Programming Manual Programming Document No: LT0122 Item Options Default AZC Time Delay 1 (Std) 2 (AVF/RAD) 3 (SAD) 4 (Delay) T1 into Alarm T2 out of Alarm 1 (Inst Alarm) 2 (Alarm) 3 (Normal) 4 (Fault) 1 (Inst Alarm) 1 Std (2.3 Sec) Delay (4) Cct B1 (0-3V) Cct B3 (13-17.
Document No: LT0122 F3200 Installation & Programming Manual Programming Item Options Default Anc 3 Relay Configuration, logic equation, Text name Supervision: disabled Latching: No Map to MAF: Yes Isolatable: Yes Testable: Yes Sup ACT: Yes No logic equation RDU Protocol RDU 1-8 LCD/non-LCD Enabled/Disabled Protocol A/B MCP Zone LCD Disabled A 1 TABLE 6.4.
F3200 Installation & Programming Manual Programming Document No: LT0122 THIS PAGE LEFT INTENTIONALLY BLANK Page 6-36 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration CHAPTER 7 PROGRAMMING SYSTEM CONFIGURATION Issue 2.
F3200 Installation & Programming Manual Programming System Configuration 7.1 Document No: LT0122 SYSTEM CONFIGURATION MENU The System Configuration menu is Option 4 in the Program Data menu (as shown in Fig 6.1.2). It allows programming of the parameters which determine the way the F3200 hardware operates. The menu includes the following: 1 Circuits (AZCs); 2 Zones; 3 Modules; 4 Output Logic; 5 Relay (Supervision); 6 RZDUs and will also include option 7:Network for a networked system. Fig 7.1.
F3200 Installation & Programming Manual Programming System Configuration 7.2 7.2.1 Document No: LT0122 CONFIGURING CIRCUITS (AZCS) GENERAL When the configure circuits option is selected, the LCD displays a message, and then automatically selects AZC 01, or the last AZC programmed. For the selected AZC it displays a list of attributes which can be programmed, and the option that is currently selected for that attribute. The list may be stepped through by use of ! " keys.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration MODE (CONTINUED) Switches in additional pull up resistor to +22V in Alarm. Suits detectors with high alarm current requirement or remote LED indicators. (Refer to Appendix A2). Mode 3 Low Current 680 Ohm pull up resistor to +22V supply. 10k EOL. Suits high resistance, low current circuit e.g. sub-indicator panel monitoring. Mode 4 Tamper 680 Ohm pull up resistor to +22V supply. Requires EOL002Z active EOL.
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 TIME DELAYS (CONTINUED) 4 Delay Depends on "into alarm time" For D1 > 0 Inst Alarm 2.3 Alarm 2.3 + D1 For D1 = 0 Inst alarm .2-.8 seconds Alarm .2-.8 seconds 2.3 D2 .2-.8 seconds D2 + .2 Default Settings for Delays Delay Type 2 AVF/RAD 3 SAD 4 DELAY D1 11 11 (V2.08 or earlier) 0 (V2.09 or later) 30 D2 65 65 0 (2.3) All times are in seconds. There is a minimum time delay of 2.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration Reset Delay When an AZC is reset, automatically (during AVF), manually, or from an output logic command, the AZC is turned off for a period of 5.1 - 5.7 seconds. 7.2.5 VOLTAGE BANDS The F3200 monitors the AZC voltage and decides the circuit status on the basis of which one of 5 voltage bands it is in, as shown in Table 7.2.1. Voltage band B2 (3V to 13V) always generates Alarm (detector operated).
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 VOLTAGE BANDS (CONTINUED) Voltage bands and their interpretation for modes 1, 2 and 3 are shown in Table 7.2.1 following. Band Voltage Status Default Status B5 21-22VFault (Open Circuit) Fault (Open Circuit) B4 17.5-21V Normal Normal B3 13-17.5V Programmable Normal (V1.XX software) Instant alarm (V2.
Document No: LT0122 7.3 F3200 Installation & Programming Manual Programming System Configuration CONFIGURING ZONES 7.3.1 GENERAL The programmable options for each zone as shown in Fig 7.1.1 are: Latch/Non-Latch; Map/Non Map to MAF/Status Only; Map/Non-Map to Anc1; Map/Non-Map to Anc2; Map/Non-Map to Bells; Map to LED. Mapping a zone to an output e.g. to ANC1 (Ancillary Relay 1) causes the output to operate when that zone goes into alarm.
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 MAPPING ZONES TO LEDS (CONTINUED) For this reason, when changing zone to LED mapping it is necessary to disable the LED mapping of the zone/relays (by selecting LED 0) which have a default mapping to the LEDs which other zones are to be mapped to. (It is suggested that the programmer works from largest zone number to smallest for this).
Document No: LT0122 7.4 F3200 Installation & Programming Manual Programming System Configuration PROGRAMMING OUTPUTS 7.4.1 GENERAL The F3200 outputs (Ancillary Relays, MAF Brigade Relays, 8 Zone Module open collectors and 8 Relay Module relays) may be programmed to operate on a logic equation of zone and FIP status. Zone LEDs may also be controlled by an output logic equation. Output logic equations may also be used to isolate, de-isolate or reset zones.
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 GENERAL (CONT’D) 3. When programming logic equations, the amount of programming memory left can be viewed by using the "free space" option of the OUTPUT LOGIC menu. 7.4.2 LOGIC OPERATORS The logic operators allowed are as follows: OR (+) C=A+B logical or C is active if A is active or B is active. AND (.) C=A.B logical and C is active if A is active and B is active.
Document No: LT0122 7.4.3 F3200 Installation & Programming Manual Programming System Configuration LOGIC OPERANDS Two types of operand exist. (Operands are items that can be used within an equation i.e. as inputs). The first is an item which requires a further qualifier e.g. Zone requires a zone number (1-64) and a condition e.g. Alarm. (The zone item and alarm condition are abbreviated to ZN and Alm in the LCD option menu, but become Z and A when entered into an equation).
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 OPERANDS TYPE 1 (CONTINUED) Notes: 1. When entering numbers, leading zeros need not be entered. 2. Alarm and Fault refer to the latched status for a latching zone and the current status for a non-latching zone. 3. None of these zone tokens are affected by the programming of a zone as MAF mapped, non-MAF or status only. 4. The circuit input refers to the "debounced" circuit input prior to the 2.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration OPERANDS TYPE 1 (CONTINUED) Zone Range (ZR) Zxx:yy(zz)q where xx, yy, zz = 1 - 64, yy > xx , (yy - xx) + 1 > zz q can be A,F,I,N,D,M,R as above. The operand returns true if the number of zones in the range xx to yy in the specified condition is zz or greater. If zz is zero at least one zone must be in the specified condition for the operand to be true (i.e. 0 and 1 are the same).
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 OPERANDS TYPE 1 (CONTINUED) Open Collector (OC) OCxx where xx = 1-64 OCxx is true if OCxx is active from its own logic equation and false if OCxx is inactive. New Alarm (NA) The New Alarm token (NA) is a set/reset latch, which incorporates two lists of tokens. One list of tokens "sets" the latch i.e. when a token goes true the latch goes true and stays true, even if the token returns to false.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration OPERANDS TYPE 1 (CONTINUED) Timers Txx where xx = 1 - 64 for seconds timers and 65-72 for minutes timers. Timers allow outputs to be timed from inputs. They all have two time delays associated with them and can be "stretch" timers or "pulse" timers, and the default configuration sets both delays to zero, and all timers are set to "false" on power up.
F3200 Installation & Programming Manual Programming System Configuration 7.4.3.2 Document No: LT0122 Operands Type 2 ACK When the "ACK" key is pressed with the base display selected this returns true for between 1 and 2 complete passes of all output logic equations. ALM True if 1 or more local MAF zones is in alarm, or true in New Zealand mode if a latched battery very low alarm is present. BEL See discussion on Bells/Anc3 in Ancillary Relay Tokens.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration OPERANDS TYPE 2 (CONTINUED) NEV New Zealand mode evac defect input true. NMA True if 1 or more non MAF-mapped zones are in alarm. NMF True if 1 or more non MAF-mapped zones or non MAF-mapped module/ancillary relays are in fault.
F3200 Installation & Programming Manual Programming System Configuration 7.4.4 Document No: LT0122 EXAMPLES OF LOGIC EQUATIONS Example 1 - Use of Variables Assume that two relays are required with similar logic equations, as follows: R1 = (Z1A + Z2A + Z9A + Z10A) .^ Z3A R9 = (Z1A + Z2A + Z9A + Z10A) .^ Z11A Rather than enter both equations in full, it is easier to assign a variable to the common section of logic and enter three equations as follows: V2 = Z1A + Z2A + Z9A + Z10A R1 = V2.^Z3A R9 = V2.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration EXAMPLES OF LOGIC EQUATIONS (CONTINUED) The logic may be entered using the zone range (ZR) option as follows: R4 = Z9:12(1)A (i.e. alert on any of zones 9-12 in alarm) V1 = (Z9:11(2)A.^Z13A)+Z12A (i.e. any two of zones 9-11 in alarm with Zone 13 not in alarm, or Zone 12 in alarm).
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 EXAMPLES OF LOGIC EQUATIONS (CONTINUED) Example 4 - Use of Timer To Make Continuous Pulsing A building has a loud "hooter" to attract the operator to the FIP. The hooter is relay driven and must pulse 1 second on, 1 second off, on occurrence of any alarm until it is acknowledged. Solution: Use a timer to make a 1 second on, 1 second off oscillator. A relay (say Anc2) and a timer (say T1) are assigned.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration ENTERING EQUATIONS (CONTINUED) 3. When an equation has been entered, check it, and count the number of "(" and the number of ")" to ensure they are the same. 4. It is recommended that all equations be written on forms (such as in Appendix B) before they are entered, and then checked against the forms after they have been entered).
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 ENTERING EQUATIONS (CONTINUED) The next relay can be selected. Note that Z9A and Z10A could have been entered as zone range ZR9:10(1)A. Entering an NA Operand To enter an NA operand, do the following: 1. Select NA with the █ in the bottom line and press "ENTER". 2. Select the first token in the "RESET" group with the cursor keys and enter it. 3.
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration THE OUTPUT LOGIC PROGRAMMING MENUS (CONTINUED) Open Collectors - 1 to 64 corresponding to the AZC boards installed. Ancillary Relay - MAF ancillary relays 1,2,3. Net Var - network variables 1 - 256 (network systems only).
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 7. Equations may be entered for relays 1-64 even through the appropriate 8 Relay Modules are not fitted. The resulting states could be sent to an RDU or another device on the RZDU bus. 8. When driving the fault relay with logic, the following should be noted. The fault relay can be controlled with logic by the equation FLT = ...
Document No: LT0122 F3200 Installation & Programming Manual Programming System Configuration CONTROLLING ZONE LEDS (CONTINUED) For example, an equation of R65=Z1:20(1)A will result in alarm LED 1 turning on steady whenever one or more zones in the range 1 to 20 has an unisolated alarm. An equation of R256=PLI , will result in isolate LED 64 turning on steady when PLANT is isolated. An equation of R129=SFT , will result in fault LED 1 turning on steady whenever there is a system fault.
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 ENTERING OUTPUT LOGIC ZONE COMMANDS (CONTINUED) When an existing equation (call it "E1") is shown, the first and/or last zone may be modified and if an equation with the new first and last zone does not already exist then the "right hand side" of equation "E1" will be copied into the new equation (call it E2). Equation E2 may then be modified if desired, or immediately saved.
Document No: LT0122 7.4.9.2 F3200 Installation & Programming Manual Programming System Configuration OPERATION OF OUTPUT LOGIC ZONE COMMANDS Reset Command A single zone or a range of zones may be reset. All zones in the specified range will be reset, regardless of whether they are in alarm or not, as if the zones had been reset by an operator from the keypad. The output logic initiates the reset command whenever the equation on the right hand side is true.
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 EXAMPLE EQUATIONS (CONTINUED) (iii) To reset a zone after it has been in alarm for 30 seconds. T1[S30:0]=Z1A ZR1:1=T1 After zone 1 alarm (Z1A) has been true for 30 seconds, timer T1 will become true and a reset command will be issued to zone 1. This will immediately cause Z1A to become false, resulting in timer T1 becoming false and removing the reset command initiation.
Document No: LT0122 7.5 7.5.1 F3200 Installation & Programming Manual Programming System Configuration RELAY SUPERVISION GENERAL The Ancillary relays (Anc1 and Anc2) and Bells relay on the MAF/PSU, and the Module relays all have the option of supervision (i.e. checking the wiring from a relay to its load to see that it is not "short" or "open" circuited). In F3200, the supervision also includes a "confirmation" function i.e. it expects to "see" a different state after a relay has been activated.
F3200 Installation & Programming Manual Programming System Configuration 7.5.3 Document No: LT0122 MODULE RELAY SUPERVISION This is option 2 of the Relay Supervision menu. To program module relay supervision the desired relay number is selected by use of the "NEXT" and "PREV" keys. The options which may be selected are: Supervision enabled (E) or disabled (D). Supervision latching (L) or non-latching (N) (i.e. the fault condition). Fault and isolate mapped (M) or not mapped to the MAF.
Document No: LT0122 7.6 F3200 Installation & Programming Manual Programming System Configuration RDU The connection of RDUs (RZDUs, Remote LCDs) to a FIP is described in Sections 2.1.6 and 8.9. An F3200 panel transmits the status of its alarm zones and module relay zones to an RDU. The F3200 panel may have from zero to 64 alarm zones and these zones are always mapped to zones 1 to 64 at the RZDU. The F3200 panel may have from zero to 64 module relays and for F3200 V2.
F3200 Installation & Programming Manual Programming System Configuration Document No: LT0122 RDU (CONTINUED) The RZDU MCP can be mapped to a FIP zone by entering a zone number. Transmitting Zone Names to an RDU F3200 V2.03 software or later and RDU V2.01 software or later allow the downloading of zone and module relay names to connected RDUs using the comms link to the RDU. This is initiated from the SET menu described in Section 6.2.1. A password is required to initiate this command.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring CHAPTER 8 INSTALLATION & WIRING Issue 2.
F3200 Installation & Programming Manual Installation & Wiring 8.1 Document No: LT0122 INSTALLATION 8.1.1 CABINET INSTALLATION The location of the F3200 FIP is chosen by the Fire Authority and building owner (or owner’s representative) in accordance with the Australian Standard AS1670.1. If the cardframe needs to be made removable to allow fitting/removing of large batteries, this should be done prior to cabinet installation. (Refer to Section 8.1.2).
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring 430 (8U Cabinet) 415 (15U Cabinet) │<───────────────────────────────>│ │ │ ┌─────────────────────────────────────────┐ ─── │ │ │ │ │ │ │ │ ───────────────│── o ─────────────────────────────── o ──│──── │ │o /6.0 o /6.
F3200 Installation & Programming Manual Installation & Wiring 8.1.2 Document No: LT0122 CARDFRAME INSTALLATION A KT0072 Cardframe upgrade kit can be fitted to a 15U F3200 to allow it to take more than three 8 way modules. In older versions, the cardframe mounts directly to the rear of the cabinet. In newer versions, the cardframe is fitted to a gear plate that may be removed when the cabinet is mounted to the wall. 1. If the system does not require large batteries (refer to Section 4.3.
Document No: LT0122 8.1.3 F3200 Installation & Programming Manual Installation & Wiring MODULE INSTALLATION The 8 Zone Modules and any 8 Relay Modules are fitted in order, from top to bottom. The FRCs fit under each PCB, from BUS OUT of the top one to Bus IN of the next one (see Fig 8.1.2). Observe the following: (a) When mounting to the cabinet the M3 mounting screw per module should be tightened firmly to earth the module. (b) Modules and FRCs need to be fitted one at a time in the Cardframe.
F3200 Installation & Programming Manual Installation & Wiring 8.1.4 Document No: LT0122 LED DISPLAY INSTALLATION When LED Displays are required, the 7U inner door (ME0060) is fitted to the standard cabinet directly below the 4U Operator Display with the M6 screws, washers and cage nuts provided. The hinge is on the right hand side. Click the cage nuts in from the inside. (7U doors cannot be fitted to a small cabinet). The flat M6 washers have a sharp edge and a rounded edge.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring ════════════════╗ ╔══════════╗ ╔══════════╗ ╔══════════╗ J13 ║ ║ ║ ║ ║ ║ ║ ┌┐ ║ LM0092 ║ ║ ║ ║ ║ ║ CONTROLLER │├──╨────┐ ║ ║ ║ ║ ║ ║ │├──╥──┐ │FRC ║ ║ ║ ║ ║ ║ └┘ ║ │ │ ║ ║ ║ ║ ║ ║ ║ │ │ ║ ZONES ║ ─ ─ ─ ║ ZONES ║ ║ ZONES ║ ════════════════╝ │ │ ║ 48 TO 64 ║ ║ 17 TO 32 ║ ║ 1 TO 16 ║ │ │ ║ ║ ║ ║ ║ ║ │ │ ║ EXT+ ║ RED ║ EXT+ ║ ║EXT ║ RED┌───┼─┼────╫─o─o──────╫───────╫─o─o──────╫──╫─o LK1 ║ │ ┌─┼─┼────╫─o─o──────╫───────╫─o─o─────
F3200 Installation & Programming Manual Installation & Wiring 8.2 Document No: LT0122 FIELD WIRING 8.2.1 GENERAL Cabling should comply with all the points in AS1670.1, Section 8.17. Note the requirements for segregation and identification. The cabling should, in general, be of not less than 0.75mm² cross sectional area, insulated and have red PVC sheathing. Joins should only occur in enclosed terminal boxes, and it is important that all terminations be good. I.e.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring FIG 8.2.2 GOOSENECK CABLING 8.2.2 MAINS WIRING The mains (240Vac) supply must be connected in accordance with AS1670.1 and AS3000 regulations. Ensure the mains cables to the FIP are isolated at the Distribution Board before connecting to the FIP. The mains cable connects to the 3 way terminal block mounted to the cabinet rear behind the mains cover. (a) Remove the mains cover with a Pozi screw-driver.
F3200 Installation & Programming Manual Installation & Wiring 8.3 Document No: LT0122 AZC WIRING Detectors must be installed and wired as per AS1670.1. Observe the requirements for conductor type and size. Connection to the particular MCPs, detectors or bases must be as specified by the manufacturer. Similarly for remote LED connection. AZCs must be wired as per Fig 8.3.1 with "In" of the first detector connected to the 8ZM, and the EOLR to the "out" of the furthest detector.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring ┌─┐ ┌──────┐ ┌──────┐ ┌──────┐ │ ├─┤ │E├───┼o+ +o┼──┼o+ +o┼── ─ ─ ─ ─ ─┼o+ +o┼────_ _──────────┤O│ + │O│ │OUT IN│ │OUT IN│ │OUT IN│ │ │ ├─┤ AZC │L├───┼o- -o┼──┼o- -o┼── ─ ─ ─ ─ ─┼o- -o┼────┼──_ _───────┤O│ └─┘ └──────┘ └──────┘ └──────┘ │ │ │ ├─┤ │ │ │ │ ┌─┐ ┌──────┐ ┌──────┐ ┌──────┐ │ │ X X │E├───┼o+ +o┼──┼o+ +o┼── ─ ─ ─ ─ ─┼o+ +o┼────┘ │ X X │O│ │OUT IN│ │OUT IN│ │OUT IN│ │ X │L├───┼o- -o┼──┼o- -o┼── ─ ─ ─ ─ ─┼o- -o┼─────
F3200 Installation & Programming Manual Installation & Wiring 8.4 Document No: LT0122 MAF ANCILLARY RELAY WIRING The original (AS1603.4) F3200 has a single Warning System output and Isolate Switch, namely the Anc3/Bells relay, configured as Bells +/-, and the “Bells Isolate” key. It is now typical for FIPs to control two outputs, i.e. a single, External Bell, and a separate building Warning System which produces tones to AS2220 (as specified in AS4428.1). The MAF module has 3 Ancillary Relays.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring WARNING Apart from the mains supply to the FIP only ELV wiring may enter the cabinet. Relays must not be used to directly switch medium or high voltage. +VNBF ┌─ | SUP | ANCIL| NC 1 | | COM └─ 0V A. WITH SUPERVISION OF LOOP POSITIVE WIRING ONLY +VNBF ┌─ | SUP | ANCIL| NC 1 | | COM └─ 0V B.
F3200 Installation & Programming Manual Installation & Wiring +VBF1 ┌─ | SUP | ANCIL| NC 1A | | NO | | COM └─ Document No: LT0122 o─────┐ │ o──┐ │ │ │ o──┘ │ │ o─────┘ LOAD (SEE NOTE) o───────────────────────────────────────────┬───────────┐ │ │ ┌┴┐ ╒╧╕ └┬┘ │ │ │ └┬┘ o───────────────────────────────────────────┴───────────┘ SUPPRESSION DIODE 0V Note: For a load of less than 400 Ohms a diode of suitable current rating must be added in series with the load at the load as shown below.
Document No: LT0122 8.5 F3200 Installation & Programming Manual Installation & Wiring WARNING SYSTEM WIRING The typical configuration allocates the Ancil 3/Bells relay to drive the Warning System, and has links Lk2-4 fitted so that a switched 24V output is available at the +/- terminals. The supervision allows for up to 3 branches of wiring, with each requiring its own end of line resistor (EOLR). The value of the EOLR varies with the number of branches such that the combined total is always 3K3.
F3200 Installation & Programming Manual Installation & Wiring Document No: LT0122 T-GEN 50 The Vigilant T-GEN 50 is permanently powered, requiring a supervised Alarm- signal from the FIP rather than switched power. The BELLS- terminal can be used for this unchanged. Alternatively, an open collector output (if the T-GEN is in or adjacent to the F3200 panel), another Ancil relay on the MAF, or an 8RM relay can be used as per Section 3.5 of the TGEN Installation Instructions, LT0186.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring EOLR 10k 2W FIRE PANEL DC IN Bells + LINE OUT + + S Bells - F3200 + 24V Mini-Gen (PA0895) EOLR 10k 2W - 2-W LINK FITTED DC IN + + S LINE OUT 24V Mini-Gen (PA0895) 2-W LINK FITTED + EOLR 10k 2W - FIG 8.5.
F3200 Installation & Programming Manual Installation & Wiring Document No: LT0122 + F3200 EOL NC NO ANCIL 3 BELLS C Normally closed Fault relay * - FIP I/P FIG 5.5.3 MICROVAC OR QE90 (* = EOL for QE90/MICROVAC) FIG 8.5.4 WIRING ANCIL 3 TO MICROVAC/QE90 NO ANCIL 3 MICROVAC QE90 EOL MICROVAC/ QE90 FIP I/P C Remove Lk2, 3, 4 on MAF + F3200 AZC - * Normally closed Fault relay MICROVAC OR QE90 (* = EOLR for F3200 AZC) FIG 8.5.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring 6Adc Batt - Fuse Bell Monitor Rev 3 0V Evac+ +V BELLS + BELLS NC EOLR Evac 0V EOLR Evac- Ext Def- 2K7 Up to 3 branches of Load. Anc 3 NO Lk2 Lk3 Lk4 Notes 1. 2. Wire an in-line fuse holder with 6A fuse from Batt+. The Bell Monitor must be Rev 3 or greater and is supplied with instructions, adhesive based stand-offs, and EOLRs. FIGURE 8.5.6 USING BELL MONITOR BOARD ON ANCIL 3/BELLS RELAY Issue 2.
F3200 Installation & Programming Manual Installation & Wiring 8.6 Document No: LT0122 MODULE RELAY WIRING The 8 Relay Module relays each have one set of voltage free change-over contacts (ie one pole) accessible via screw terminals, to switch plant equipment. The second pole of each relay can be accessed by fitting a 3-way de-mountable connector block pair CN0488 and CN0206.
Document No: LT0122 8.6.1 F3200 Installation & Programming Manual Installation & Wiring DUAL POLE – POLARITY REVERSAL OUTPUT Two relays; or 1 relay, an open collector output and an external 2 pole relay (e.g. PA0730); can be arranged to provide a supervised dual-polarity output suitable for driving dual strobes (Alert and Evacuate) or some visual warning devices (e.g. an AVI). The output is normally off (supervising voltage only), but can turn on with 24V in one polarity or in the other polarity.
F3200 Installation & Programming Manual Installation & Wiring 8.7 Document No: LT0122 OPEN COLLECTOR WIRING 8.7.1 LED MIMIC DISPLAYS It is expected that the most common use the open collector outputs will be to switch LEDs on "mimic" displays. These outputs are approved for field connection, so may be used to "drive" remote mimics. Typical connection is shown in Fig 8.7.1. 8.7.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring │ OCn ─┬─ ┌┴┐ │ │ │ │ └┬┘ ┌─┴─┐ +┌─┴─┐ │ │ ├───────────────────────────────┤ ├───┴────────────────────── └─┬─┘ └─┬─┘ │ Cct n │ │ │ EOLR │ 0V F3200 ┌─┴─┐ ┌─┴─┐ │ ├───────────────────────────────┤ ├───── 0V └─┬─┘ └─┬─┘ │ │OTHER EQUIPMENT FIG 8.7.2 EXAMPLE OF INTERFACING TO OTHER EQUIPMENT, DIRECT COUPLING ┌───┐ │ ├───────────────────────────┐ OPTOCOUPLER └───┘ ┌┴┐ ┌───┐ RESISTOR │ │ ┌─────┤ │+ E.G.
F3200 Installation & Programming Manual Installation & Wiring 8.9 Document No: LT0122 RDU WIRING A FIP may drive up to 8 Remote Display Units (RDUs) that are programmed to send information back to the FIP. More "monitoring only" devices may be connected to the FIP RZDU Tx line. Some RDUs have their own power, but others require their power (24Vdc) to be supplied from the FIP or an approved PSU with battery backup. The RDUs are all connected in parallel on common Tx and Rx circuits.
Document No: LT0122 F3200 Installation & Programming Manual Installation & Wiring FIP J11 FP0558 MAF CONFIGURED RDU MAF Bd connector J11 (Cut Lk1 on MAF/PSU) ┌─┐ ┌─┐ ╔══════════════╡O│+VBF2 │O│+VBF2 ║ ├─┤ ├─┤ ║ ╔══════╡O│TX ╔══════════════════╡O│TX RZDU ║ ║ ├─┤ ║ ├─┤ COMMS ╔═══╬═══════╬══════╡O│0V ║ ╔═════════════╡O│0V ║ ║ ║ ├─┤ ║ ║ ├─┤ ║ ║ ╔════╬══════╡O│RX ║ ║ ╔════════╡O│RX ║ ║ ║ ║ └─┘ ║ ║ ║ └─┘ ║ ║ ║ ║ ║ ║ ║ ║ ║ ║ ║ ║ ║ ║ ║ ║ █════╣════════════════════╝ ║ ║ ║ ║ ║ ║ ║ ║ █═══╬══╬════╬══════════════════
F3200 Installation & Programming Manual Installation & Wiring 8.10 Document No: LT0122 SLIMLINE NDU (FP0714) WIRING MCP Connection A slimline NDU has the facility for connection of an MCP, but the MCP has to be mounted on the wall, immediately adjacent to the NDU. Connection is made to pins 3 & 4 of J5, the 4 way "Spare Input Connector" on the NDU Controller/Display Bd. The wiring to the MCP itself is detailed in the figure below. For an NDU in New Zealand mode refer to Chapter 12. FIG 8.9.
Document No: LT0122 F3200 Installation & Programming Manual Applications CHAPTER 9 APPLICATIONS Issue 2.
F3200 Installation & Programming Manual Applications 9.1 Document No: LT0122 AS1668 AIR CONDITIONING CONTROL 9.1.
Document No: LT0122 F3200 Installation & Programming Manual Applications FIG 9.1.2 F3200 WITH TYPICAL AS1668 PANEL (10 UNITS) 9.1.2 CIRCUITS & ZONES FIP End Inputs The "off", "auto" and "on" inputs from the AS1668 Control Module can be connected to 0, 1 or 2 AZCs as desired.
F3200 Installation & Programming Manual Applications Document No: LT0122 CIRCUITS & ZONES (CONTINUED) The option in Fig 9.1.3 A could be implemented by "tacking" the 560E resistor (or 6V8 Zener) onto the pcb. The 2 AZC option (Fig 9.1.4) could also be implemented by soldering the extra resistor and wires onto the unused contact of the rotary switch on the pcb. In all cases, "auto" is zone "normal".
Document No: LT0122 F3200 Installation & Programming Manual Applications CIRCUITS & ZONES (CONTINUED) For options A and C in Fig 9.1.3, configure circuit Alarm Text as "manual" and voltage band B1 as "Instant Alarm" (refer to table below). Voltage Band Default State B5 B4 B3 B2 B1 Fault Normal Alarm Program State Fan Control Normal Switch wiring open circuit "Auto" "Auto" "Off" "On" Inst Alarm Configure the zone as non-latch, Status, non Anc1/Anc2/Bells.
F3200 Installation & Programming Manual Applications Document No: LT0122 CIRCUITS & ZONES (CONTINUED) Where a "Fault" contact is available, along with "Run", both can be put onto a single AZC with the NO "Fault" contact shorting the AZC and voltage band B1 programmed as "Fault" (refer to Fig 9.1.5 A). Alternatively, the NC "Fault" contact can be put in series for open circuit Fault, and the NO "Run" contact can short the AZC, with B1 programmed as "Alarm" (ZnD). (Refer to Fig 9.1.5 B).
Document No: LT0122 F3200 Installation & Programming Manual Applications CIRCUITS & ZONES (CONTINUED) R5 = Z15D + Z15N.Z5A.^ (Z1:4(1)A+Z6:10(1)A) Note also, that if the interposing relay (fan control input) is 24V at less than 100mA then an open collector (O/C) may be used as per circuit 1 of 1945-1-1/4 following. 9.1.4 LEDS The 3 LEDs may be: switched directly as per circuits 1 and 2 of 1945-1; driven off 3 open collector (O/C) outputs or driven off 2 O/Cs with a Zener diode as shown in Fig 9.1.
F3200 Installation & Programming Manual Applications Document No: LT0122 CIRCUITS & ZONES (CONTINUED) Note that the logic requested for the LEDs in Option B is as follows: LEDs RUN off on x FAULT off x on OUTPUTS STOPPED on off x OC1 off on x OC2 off x on Where x = off or on (don't care). 9.1.5 AS1668 CONTROL MODULE & DRAWINGS The following drawings are of 4 typical configurations using the AS1688 Control Module, 1945-1.
+24V (RED) 1 TO OTHER AS1668 CONTROL/INDICATORS (RED) +24V (RED) +24V (RED) 1 AFS +24V C 5V6 BZX55 A 1N4148 LD3 RED "RUN" TO OTHER AS1668 CONTROL/INDICATORS 1 LOAD (+) 1 AFS (RED) +24V AIR FLOW SWITCH (GREEN) 1 LD1 GRN "STOP" (BLACK) 1 0V AUTO CONTROL 1 0V (BLACK) 1 LOAD (FAN) O/C = 0.
RLY (COM) 1 +24V SWITCHED (ORANGE) (ORANGE) 1 (GREEN) 1 LOAD (+) SUPERVISED RELAY OUTPUT 1 1 +24V SW RLY (NO) BOTH 1 +24V +24V (RED) 1 +24V IN C 3K3 TO OTHER AS1668 CONTROL/INDICATORS 5V6 COMPONENTS POSITION B 3K3 +24V (RED) LD1 GRN "STOP" LD3 RED "RUN" I 5V6 BZX55 LD2 YEL "FAULT" F 1N4148 O 1N4148 AFS 1 LOAD (FAN) AFS AIR FLOW SWITCH CLOSE FOR RUN 1 1 AFS 0V 1A MAX OFF SW1 UNLESS OTHERWISE STATED: (BROWN) 1 AUTO Q REOL FIT AS REQUIRED ON AZC - 1 (BLACK) 0V 1
RLY (COM) 1 +24V SWITCHED (ORANGE) (ORANGE) 1 LOAD (+) SUPERVISED RELAY OUTPUT 1 RLY (NO) 1 +24V TO OTHER AS1668 CONTROL/INDICATORS +24V (RED) 1 +24V C 3K3 +24V B 3K3 (RED) 1 OPEN COLLECTOR 1 (BLUE) 1 LD3 RED "RUN" RUN O/C LD1 GRN "STOP" LD2 YEL "FAULT" I 5V6 BZX55 1 OPEN COLLECTOR 2 (YELLOW) 1 0V (BLACK) 1 1 + 1A MAX OFF SW1 (BROWN) 1 I/P AUTO AZC1 ON - + 1 (BLACK) 1 (VIOLET) 1 I/P COM Q REOL FIT AS REQUIRED PA0728 1945-1-3 1 AFS(+) REOL AZC2 UNLESS
RLY (COM) +24V SWITCHED 1 (ORANGE) (ORANGE) LOAD (+) 1 SUPERVISED RELAY OUTPUT 1 RLY (NO) TO OTHER AS1668 CONTROL/INDICATORS +24V 1 +24V (RED) +24V 1 C 3K3 +24V A 3K3 B 3K3 (RED) LD3 RED "RUN" OPEN COLLECTOR 1 OPEN COLLECTOR 2 OPEN COLLECTOR 3 1 (BLUE) 1 (YELLOW) 1 1 (GREEN) 1 LD1 GRN "STOP" LD2 YEL "FAULT" RUN O/C 1 LOAD (FAN) FAULT O/C STOP O/C 1A MAX STOP SW2 + 1 (BROWN) 1 I/P AUTO AZC1 - + UNLESS OTHERWISE STATED: RUN 1 (BLACK) 1 (VIOLET) 1 I/P COM Q
Document No: LT0122 9.2 9.2.1 F3200 Installation & Programming Manual Applications GAS FLOOD GENERAL The following features of the F3200 make it well suited to "Gas Flood" control: • • • • • • • • • • • AZC Alarm Text for "pressure switch", "manual", can be used for the various inputs; Zones can be programmed as latch/non-latch, MAF/non-MAF as required, e.g. non-latch, non-MAF, for "Gas Inhibit" input; Zone range operand allows easy programming of "voting systems" on detector circuits e.g.
F3200 Installation & Programming Manual Applications Document No: LT0122 LOGIC & CONFIGURATION (CONTINUED) Relay 1 = Alert O/P (1st stage sign FIRE ALARM) Relay 2 = Evac O/P (2nd stage sign EVACUATE and DO NOT ENTER) Relay 3 = Gas Release Solenoid Relay 4 = System Inoperative sign Isolate = Guard Relay (see note 2) Timer T1 [S30:0] = V1 30 Second time delay from "Gas Initiated" (second stage). Variables V1 = Z1A.Z2A.
Document No: LT0122 F3200 Installation & Programming Manual Applications LOGIC & CONFIGURATION (CONTINUED) Configure Relay Supervision Relay Enable Latch MAF LED Isolate Test Sup.Act Gas Release Y - - - - - - By default, relays are isolatable and testable but this can be changed if desired. For all configuration, only items that have to be changed from default are shown. 9.2.3 NOTES 1.
F3200 Installation & Programming Manual Applications Document No: LT0122 NOTES (CONTINUED) 9. If a Lock-off valve is not required, then Z7 is not required and can be left out of the equations. Note that AS4124.1 requires the Lock-off Valve to isolate both poles of the Gas Release solenoid / actuator. This is not done within the ME wiring and would therefore need to be done externally with microswitches (or a relay). 10. The standard LCS Gas Start switch automatically turns on when the glass is broken.
Document No: LT0122 F3200 Installation & Programming Manual Applications USE OF ACTUATORS (CONTINUED) The maximum number of actuators connected in series in one circuit is dependent on the cable resistance. The following are estimates for the Metron Protractor and 427354 current limiter, and are not confirmed by the manufacturer (consult the manufacturer). Allow: 21V as worst case battery voltage; 6.5V drop for regulator; 2.5V drop per actuator; 1V drop for diode EOL; 1V per Ohm of cable resistance.
F3200 Installation & Programming Manual Applications Document No: LT0122 AVI SIGNS (CONTINUED) Function Input Lamps Tone Lk3 Lk6 Alert Evac Mode DIL SW DIL Sw Lk1,2 On Off 3-wire 1,3,5,6 2,4,7,8 1-2 std 1 AlertBoth Top Both 1-2 On 2 AlertBoth Top Both Alert Evac 3-wire 1,3,5,6 2,4,7,8 std 1-2 1-2 On 3 Evac- Both Evac 2-wire 2,3,5,6 1,4,7,8 2-3 1.2 Off 4 Alert- Both None 3-wire 1,3,5,6, spcl 8 1-2 2-3 On 2,4,7 Notes b. Notes a.
Document No: LT0122 F3200 Installation & Programming Manual Applications FIGURE 9.2.1 GAS FLOOD LOGIC DIAGRAM Issue 2.
F3200 Installation & Programming Manual Applications Document No: LT0122 FIG 9.2.2 LOCAL GAS CONTROL STATION, FRONT VIEW Page 9-16 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Applications Notes 1. 2. 3. Only the wiring to AVIs making tones is supervised (the Sync wire is not supervised). The supervising relays should be programmed to not supervise in the activated state. This AVI should be mounted upside down, with the DNE face plate up the right way. FIGURE 9.2.5 WIRING MULTIPLE SUPERVISED 2 STAGE SIGNS Issue 2.
F3200 Installation & Programming Manual Applications Document No: LT0122 Notes 1. 2. 3. 4. The second pole of the relay is used by fitting connectors CN0260, CN0488 to the holes in the 8RM. If only one sign is used, the diode need not be fitted. Both tones should be disabled in the AVI. If Supervision is not required, the second pole is not required and the AVI +24V terminal can be wired directly to the Gas Flood +24V terminal. FIGURE 9.2.
Document No: LT0122 9.3 F3200 Installation & Programming Manual Applications SUB FIP MONITORING 9.3.1 GENERAL A sub-FIP is a Fire Indicator Panel (e.g. a Gas Flood Panel) which may not be connected directly to the Brigade, but repeats its common conditions (e.g. Fire, Fault) to another FIP. AS1670.1 allows for the cabling from FIP to sub-FIP to be less than 0.75sqmm, and the resistance may be considerably greater than that used in standard detector circuits.
F3200 Installation & Programming Manual Applications 9.3.2 Document No: LT0122 CONNECTION There are various connection possibilities depending on the particular local requirements for Standby and Isolate, and the loop resistance. One or two AZCs may be required. Where Standby is required as a separate signal at the Main FIP it can be signalled as Alarm on a second AZC and the corresponding zone programmed as non-MAF, non-Anc1, etc. Isolate could be signalled as "Fault" on the same AZC (ref Fig 9.3.
Document No: LT0122 F3200 Installation & Programming Manual Applications FAULT ISOLATE ┌──┐ ┌─────────o──o───────o──o──────┬──────────┬───────┤ │+ │ (NC) (NC) │ │ └──┘ │ │ │ │ │ │ ┌┴┐ o STDBY o ALARM 2K7│ │ / (NC) / (NO) AZCn └┬┘ o o │ ╒╧╕ │ │ 5V6 OR 470E │ │ │ │ └┬┘ │ ┌──┐ └──────────────────────────────┴──────────┴───────┤ │└──┘ Program B1 as Instant, ZnM represents "Alarm" ZnD represents "Standby" ZnF represents "Fault" or "Isolate" FIG 9.3.
F3200 Installation & Programming Manual Applications 9.4 Document No: LT0122 FIRE DETECTION IN HAZARDOUS AREAS (EXPLOSIVE ATMOSPHERES) 9.4.1 REFERENCES AS 2380 Electrical Equipment for Explosive Atmospheres - Explosion-Protection Techniques. AS 2381 Electrical Equipment for Explosive Atmospheres - Selection, Installation & Maintenance. AS 2430 Classification of Hazardous Areas. IEC79 Electrical Apparatus for Explosive Atmospheres. SAA HB13 Electrical Equipment for Hazardous Areas (handbook).
Document No: LT0122 9.4.3 F3200 Installation & Programming Manual Applications INTRINSICALLY SAFE DETECTION There are two types of device which may be inserted in a detector circuit between the FIP and the detectors to limit the electrical energy flow into the area and provide IS detection: 1) Galvanically (transformer) isolated repeaters (isolators). 2) Zener barriers (shunt barriers with fuses). These limit the circuit voltage relative to earth, and the circuit current.
F3200 Installation & Programming Manual Applications Document No: LT0122 ISOLATED REPEATERS (CONTINUED) DETECTOR CAPACITANCE INDUCTANCE C29BEx/Z94C R24Bex FW68 FW105 FW180 S231i+ S121 MS302Ex MF301Ex MR301Ex (Photo) MR301TEX (HPO) T56B (Heat) (Z500N base) T54B (Heat) 1Nf 3.3nF 84nF/km 66nF/km 57nF/km 1.5nF 4nF 1.5nF 1.5nF 1.5nF 1.5nF 0 0 0 1uH (0.001mH) 1.5mH 0.62mH/km 0.83mH/km 0.89mH/km 0 0 0 0 0 0 0 0 0 RESISTANCE (FW ONLY) 100Ω/km 100Ω/km 100Ω/km TABLE 9.4.2 CAPACITANCE & INDUCTANCE PER I.S.
Document No: LT0122 9.4.3.2 F3200 Installation & Programming Manual Applications 6 TERMINAL ISOLATED REPEATER The following 6 terminal isolating repeaters can connect an F3200 zone to an IS detection circuit using the circuit of Figure 9.4.3.2. Pepperl & Fuchs Pepperl & Fuchs KHD3-ICR/Ex130 200 KFD2-CR-Ex1.30 200 OR FIG 9.4.3.2 F3200 IS CIRCUIT USING 6-TERMINAL REPEATERS Relay or Open Collector For each AZC there must be either: a corresponding relay (e.g.
F3200 Installation & Programming Manual Applications Document No: LT0122 6 TERMINAL ISOLATED REPEATER (CONTINUED) Programming & Limitations All detector types require the circuit to be programmed for Mode 1 (Std) with voltage band B1 programmed as Alarm. The open collector must be programmed as OCn = ^ZnR, or the Relay must be programmed as Rn = ZnR (i.e. Zone n not in Reset or Zone n in Reset respectively). There can be no differentiation of voltage bands (B1, B2, B3) i.e.
Document No: LT0122 F3200 Installation & Programming Manual Applications 6 TERMINAL ISOLATED REPEATER (CONTINUED) Notes 1. Circuit lengths quoted are from the isolator to the EOL. An extra 50 Ohms of cable from the FIP to the isolator is also allowed (1.5km of 1.0mm², 1.1km of 0.75mm²). The length quoted is the maximum for the corresponding quantity of detectors. 2. Cable resistance shown is for the circuit, ie. both cables in the pair. The value of 34Ω per km (return) is used for 1 mm². 3.
F3200 Installation & Programming Manual Applications Document No: LT0122 4-Terminal Isolating Repeater Panel 24V { ZAU401 (Rev 2) (PA0838) + + To Panel Zone Circuit EOL* - 1 BATT+ 2 ZONE+ 3 EOL+ 4 EOL5 ZONE6 BATT- T+ 3 TC 2 T- 1 + - KHD0_ OR KFD0_ OR MTL5061 Ex DETECTOR Ex DETECTOR EOL 3k9 5% * EOL to suit Panel SAFE AREA HAZARDOUS AREA FIG 9.4.3.3 F3200 WITH ZAU401 & 4 TERMINAL IS REPEATER Programming & Limitations The circuit should be programmed as Mode 1 (standard).
Document No: LT0122 F3200 Installation & Programming Manual Applications 4 TERMINAL ISOLATED REPEATER WITH ZONE ADAPTOR UNIT ZAU401 (REV 2) (CONTINUED) GAS GROUP 11A OR 11B DETECTOR TYPE SMOKE PART C29BEx GAS GROUP 11C CCT LENGTH QTY BASE Z94C 40(M) 1.0mm² 3km(R) (100Ω) CCT LENGTH QTY 0.75mm² 2.2km(R) (100Ω) 40(M) 33 20 1 FLAME R24BEx - 2(M) HEAT FW105 - - HEAT T54B - HEAT T56B Z500N 40(M) HEAT S231i+ - 40(M) 4(M) 0.5km(R) (17Ω) (100Ω TOT) 3km(R) (100Ω) .
F3200 Installation & Programming Manual Applications 9.4.3.4 Document No: LT0122 4 TERMINAL ISOLATED REPEATER ALONE When all the detectors on the IS circuit will generate a short circuit alarm condition it is possible to use the lower-cost, 4-terminal isolating repeater without a ZAU401. This is shown in Figure 9.4.3.4. The following 4-terminal isolating repeaters can be used. (Note that dual channel repeaters have two separate repeaters, and can connect two circuits to the panel).
Document No: LT0122 F3200 Installation & Programming Manual Applications 4 TERMINAL ISOLATED REPEATER ALONE (CONTINUED) DETECTOR GAS GROUP 11A OR 11B GAS GROUP 11C CCT LENGTH TYPE PART HEAT FW105 HEAT HEAT T54B T56B BASE QTY 1.0mm² 0.75mm² - - NOTE 2 & 3 NOTE 2 & 3 (68Ω TOT) (68Ω TOT) 2km(R) 1.5km(R) (68Ω TOT) (68Ω) 2km(R) 1.5km(R) (100Ω) (68Ω) - Z500N 40(M) 40(M) CCT LENGTH QTY - 40(M) 40(M) 1.00mm² 0.75mm² 1.3km TOT 1.3km TOT (130nF) (130nF) 1.3km(C) 1.
F3200 Installation & Programming Manual Applications 9.5 Document No: LT0122 USE OF NORMALLY CLOSED CONTACTS There may be some situations where it is necessary to monitor a set of normally-closed contacts which open on "alarm". As standard these cannot be wired directly to the F3200 AZC terminals. The Vigilant Contact Conversion Module (part number PA0443) may be used as a conversion interface between the contacts and an F3200 AZC. This small, encapsulated module has three wires protruding from it.
Document No: LT0122 9.6 F3200 Installation & Programming Manual Applications SPECIAL CONNECTIONS TO DETECTORS 9.6.1 CONNECTING THE S231I+ OR S231F+ (USING ZAU401 REV 2) **WARNING** Even though the S231i+ is listed as hazardous area rated, this compatibility is for a direct connection – not through an intrinsically-safe isolator, and thus cannot be used in hazardous area applications. For IS applications refer to Section 9.4. The S231i+ and S231f+ detectors are not directly compatible with the F3200.
F3200 Installation & Programming Manual Applications Document No: LT0122 THIS PAGE INTENTIONALLY LEFT BLANK Page 9-34 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Alignment, Adjustment & Placing into Operation CHAPTER 10 ALIGNMENT, ADJUSTMENT & PLACING INTO OPERATION Issue 2.
F3200 Installation & Programming Manual Alignment, Adjustment & Placing into Operation 10.1 Document No: LT0122 ALIGNMENT & ADJUSTMENT All the F3200 modules (pcbs) are tested and aligned in the factory before being supplied to the customer or fitted to a FIP. The only field adjustments that may be necessary are to set the LCD contrast and the battery charger voltage. Controller/Display VR2 LCD Contrast Adjust for best readability of the LCD when viewed from the front of an installed FIP.
Document No: LT0122 10.2 F3200 Installation & Programming Manual Alignment, Adjustment & Placing into Operation PLACING INTO OPERATION 10.2.1 GENERAL This chapter describes the procedure to place an F3200 FIP into operation. It assumes that the mains and other field wiring has been connected, but that the battery has not. Note that all electronic modules were tested and adjusted in the factory and should need no further adjustment. Before switching on power, inspect the cabinet and internals.
F3200 Installation & Programming Manual Alignment, Adjustment & Placing into Operation 10.2.2 Document No: LT0122 POWER UP To place the F3200 FIP into operation, perform the following steps: STEP 1 Ensure that the Mains Isolate Switch is OFF. STEP 2 Ensure that 240 VAC is connected to the panel from the mains distribution switchboard. STEP 3 Ensure that Lk7 on the controller is set to the DATABASE WRITE PROTECT position before powering on the panel.
Document No: LT0122 10.2.3 F3200 Installation & Programming Manual Alignment, Adjustment & Placing into Operation COMMISSIONING CHECKLIST The following checklist should have been completed and supplied by the manufacturer. It should be placed with other System Configuration Information. Commissioning staff should check the installed FIP against it. (Note that all pcbs are electronically tested and adjusted before being fitted to the FIP). 1.
F3200 Installation & Programming Manual Alignment, Adjustment & Placing into Operation Document No: LT0122 COMMISSIONING CHECKLIST (CONTINUED) 3. POWER SUPPLY A) Mains Wired correctly, MOV, cap fitted B) "Mains Isolate Switch" and "NAE" label fitted C) Mains Earth wired to stud, good contact D) Mains Switch neon off/on for switch off/on E) MAF/PSU Mains On LED on, Fuse Blown LED off F) VRECT at DC IN tab 40-42Vdc G) Charger Voltage 27.25-27.4V warm, 27.5-27.75V cold 4.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming CHAPTER 11 NETWORK PROGRAMMING Issue 2.
F3200 Installation & Programming Manual Network Programming 11.1 Document No: LT0122 INTRODUCTION 11.1.1 PANEL-LINK NETWORK Networking enables up to 64 F3200 FIPs to be interconnected via single or duplicated 2 wire connections, and information to be exchanged between FIPs. Alarms occurring on any FIP on the network may be displayed and acknowledged on the LCD FFCIF of any other FIP.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming Network Application Overview (Continued) The menu includes the following options: 1. Config, 2. SIDs, 3. MAF, 4. Cmds, 5. FFCIF, 6. Events, 7. Net-variables, 8. Status; 1. Config defines the network type, the critical timing parameters, whether this panel sends link integrity messages, and the group membership for this panel. 2.
F3200 Installation & Programming Manual Network Programming 11.2 Document No: LT0122 PROGRAMMING METHODS 11.2.1 DATA FILTERS - THE SID LIST & GROUPS LIST The Panel-Link network utilises a number of concepts to allow a network designer to determine not only what information gets onto the network, but where that information can be used.
F3200 NETWORK PROGRAMMING MENU STRUCTURE FIGURE 11.1.1 F3200 NETWORK PROGRAMMING MENU STRUCTURE FOR V2.xx SOFTWARE 19 MARCH 1999 LT122P1.
F3200 Installation & Programming Manual Network Programming Document No: LT0122 NETWORK MAF STATUS (CONTINUED) 5. System fault state. True if any system fault is present. When true, this will cause any panel on the network which is programmed to use the MAF data from this panel, to energise the MAF fault relay and, (if the receiving panel is an F3200 panel), to turn its buzzer on when a new fault occurs. 6. Brigade test state.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming NETWORK MAF STATUS (CONTINUED) BLI - true if the bells are isolated at this panel or if the bells are silenced from the network. A bells silence state received from a network panel will be applied at this panel if 1. “use maf status” is enabled at this panel for the remote panel and 2. this panel has “allow receive net bells silence” enabled. (Refer Section 11.5.3).
F3200 Installation & Programming Manual Network Programming Document No: LT0122 PROGRAMMING METHODOLOGY (CONTINUED) 4) Determine whether acknowledge of broadcasts is to be enabled. Some of the messages transmitted on the network are "broadcast" i.e. not directed to one particular SID but to all SIDs. A single device on the network may be programmed to acknowledge these broadcast messages to provide some confirmation that the broadcast message was received by other devices.
Document No: LT0122 11.3 F3200 Installation & Programming Manual Network Programming NETWORK CONFIGURATION MENU These configuration settings determine how the F3200 communicates with other panels on the network. In general, most settings should be left at default values. However, there may be some settings that need to be customised for some installations. The < and > keys allow movement between five menus NetPg1 through NetPg5. 11.3.1 NETPG1 OPTIONS 1.
F3200 Installation & Programming Manual Network Programming 11.3.3 Document No: LT0122 NETPG3 OPTIONS 1. Link TX : (Yes/No) This controls whether the F3200 sends Link Integrity messages. This should be enabled for every panel. 2. Link TX time : (1-250) Time period (in seconds) between successive Link Integrity Transmissions from this SID. 3.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming NETPG4 OPTIONS (CONTINUED) For 1-12 devices, select 8 slots For 13-24 devices, select 16 slots For 25 or more devices, select 32 slots 5. Mode B This is a numeric value 0-7 which is used to control some of the network operations as follows. This value should be changed only under instruction from a systems engineer. For normal operation a value of 3 should be used.
F3200 Installation & Programming Manual Network Programming 11.4 Document No: LT0122 SID CONFIGURATION Up to 64 panels may be configured on the Panel-Link network, and each panel must have a unique SID (System Identification) number. In general, the SID number of every device on the network should be entered into the SID list of this panel and should have "Link RX" enabled (section 11.4.2). This allows this F3200 to monitor all other devices on the network.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming SID MENU ONE (CONTINUED) If the F3200 is programmed to receive FFCIF events from a particular SID, then it is also able to send Ack, Reset and Isolate commands for the event back to the originating SID (providing that reset and isolate of remote alarms is also enabled - refer section 11.7 FFCIF config). 5. TX CMD : (Yes/No) If enabled this allows this panel to send commands to the selected SID.
F3200 Installation & Programming Manual Network Programming 11.5 Document No: LT0122 NETWORK MAF CONFIGURATION As described in section 11.2.2, a panel will transmits its MAF status and totals onto the network for use by other panels, if programmed to. If both the “Refresh Tx Time” and the “Max COS rate” listed below are zero then this panel will not transmit MAF status. The MAF status and totals are transmitted at regular intervals, defined by the 'Refresh TX time'.
Document No: LT0122 11.6 F3200 Installation & Programming Manual Network Programming NET COMMANDS The Network Command configuration provides some parameters involved in the sending and receiving of commands to/from other devices on the network. When F3200 issues a command, it may take some time for the message to be sent on the network, processed by the receiver, and the response sent back.
F3200 Installation & Programming Manual Network Programming 11.7 Document No: LT0122 NET FFCIF CONFIGURATION This determines whether FFCIF alarm events are sent onto the network, and can provide an extra level of confirmation that alarm events have been received by one or more devices on the network.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming FFCIF CONFIGURATION (CONTINUED) 3. Remote ACK : Yes/No If enabled, this allows alarms in the local FFCIF alarm list to be acknowledged by commands from remote network devices. If disabled, then any alarm which is entered into the local FFCIF alarm list must be acknowledged locally - this applies to both alarms generated by local zones and alarms which come from remote devices.
F3200 Installation & Programming Manual Network Programming 11.8 Document No: LT0122 NETWORK EVENT CONFIGURATION The network event parameters determine the transmission of event log information onto the network. When an event occurs, (e.g. zone isolate, zone alarm, system test fail etc.), the event is logged into the local history queue and printed on the local event printer (if event printing is enabled - refer section 6.4.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming NETWORK EVENT CONFIGURATION (CONTINUED) Options under Events2 1. Zone/relay cmd text tx : (Yes/No) If enabled, the text name of the zone or relay will be transmitted onto the network along with the event for zone/relay command event types. "Command" type events include isolate, deisolate, reset, alarm test, fault test, operate test, auto reset test. 2.
F3200 Installation & Programming Manual Network Programming 11.9 Document No: LT0122 NETWORK LOGIC VARIABLES Network Variables can be used to transfer output logic status between panels for applications such as: (i) Fan controls. (ii) Remote zone mimics. (iii) Transfer of zone alarm status between panels. (iv) Transfer of alarm status to a common Evacuation Panel interface. (v) Transfer of brigade relay status for multiple brigade interfaces at one panel.
Document No: LT0122 11.10 F3200 Installation & Programming Manual Network Programming NET STATUS REFRESH The Network Status application provides a continual refresh of zone status onto the network. This information may be used for example, by colour graphics systems to display zone status. Enabling of the Network Status application is only necessary when there is a device on the network, eg. some colour graphics systems, that require this information.
F3200 Installation & Programming Manual Network Programming 11.11 Document No: LT0122 NDU OPERATION An NDU can be thought of as an F3200 FIP without any alarm zone modules or relay modules. An NDU also has an option of MAF board present/not present. An NDU can be programmed to operate in “New Zealand” mode rather than the default Australian mode. New Zealand mode operation is described in Chapter 12.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming NDU OPERATION (CONTINUED) Network setup The parameters for Link TX time, Link RX time, groups etc should be programmed as for a standard F3200. Network SID configuration. All 8 items that can be enabled per SID are relevant to an NDU and should be enabled or disabled as necessary.
F3200 Installation & Programming Manual Network Programming Document No: LT0122 11.
Document No: LT0122 F3200 Installation & Programming Manual Network Programming Item Parameters Default Network Event Config Transmit events Transmit event updates Transmit relay operates Zone/Relay cmd text tx Zone/Rly event text tx System event text tx Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No No No No No No Yes Network Variable Config TX enabled TX Refresh Rate Max COS TX rate Yes/No 0-255 seconds 0-250 seconds No 20 5 Network Status Config Refresh enabled TX Refresh Rate Fast TX rate Yes/No
F3200 Installation & Programming Manual Network Programming Document No: LT0122 THIS PAGE INTENTIONALLY LEFT BLANK Page 11-26 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual New Zealand Operation CHAPTER 12 NEW ZEALAND OPERATION Issue 2.
F3200 Installation & Programming Manual New Zealand Operation 12.1 Document No: LT0122 GENERAL New Zealand mode operation may be enabled on an NDU but not on an F3200 fire panel. An NDU with New Zealand mode enabled may be connected to a Panel-link network of panels which also have “New Zealand” mode enabled. The NDU may be used with or without a MAF board, and optionally with a NZ Display Extender board. The NDU may not have any RZDU or RDU connected to it.
Document No: LT0122 F3200 Installation & Programming Manual New Zealand Operation DISPLAY EXTENDER BOARD (CONTINUED) Services Restore When the Services Restore input is activated, the BSR logic token is set true and this can be used in output logic to turn outputs off or on if necessary. Trial Evac When the Trial Evac input is activated, the Bell relay is energised and the BEL logic token is set true regardless of any silence alarms or bells isolate condition.
F3200 Installation & Programming Manual New Zealand Operation 12.3 Document No: LT0122 MANUAL CALLPOINT (MCP) An NDU with a MAF board may have an MCP connected to the MAF board (refer Fig 12.3.1 for wiring). An NDU without a MAF board may have an MCP connected to screw terminals 3 and 4 of standalone connector J5 on the Controller board as shown in Fig 12.3.2. The MCP is disabled by default. To enable it, it should be mapped to one of the 16 alarm zones (1-16) on the NDU.
Document No: LT0122 12.4 F3200 Installation & Programming Manual New Zealand Operation PROGRAMMABLE OPTIONS There are a number of parameters that need to be set for New Zealand operation according to the installation requirements. These are detailed below. Fig 6.1.2D2 shows that they are accessed by selecting option 3:Global data, then 5:more, 4:more, 4:more, then 4: New Zealand options. A database re-initialise will select New Zealand mode by default if a New Zealand Display Extender board is fitted.
F3200 Installation & Programming Manual New Zealand Operation Document No: LT0122 PROGRAMMABLE OPTIONS (CONTINUED) (d) Daily battery test This is enabled by default. When enabled, every 24 hours (beginning at the auto test start time) the charger voltage is reduced for 40 minutes and the battery voltage is monitored. Parameter Defaults for New Zealand Mode The following is a list of the values set when New Zealand mode is enabled by a database re-initialise or when New Zealand mode is manually enabled.
Document No: LT0122 12.6 F3200 Installation & Programming Manual New Zealand Operation SYSTEM STATES & INDICATIONS Faults, alarms and system faults can be recalled using the Recall key. A recall of system faults will display in addition to system faults, any system states (such as trial evac) that are present.
F3200 Installation & Programming Manual New Zealand Operation Document No: LT0122 SYSTEM STATES & INDICATIONS (CONTINUED) 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. An off normal state is indicated (also defect) for approximately 10 seconds after any restart of the panel.
Document No: LT0122 12.7.1 F3200 Installation & Programming Manual New Zealand Operation THE SID LIST Normally, all other panels on the network are entered into the SID list of the NDU, with 8 options able to be set for each panel. If the NDU is the brigade connection point of the system, then probably all 8 options will be enabled for every SID in the list. When the option “use MAF relay data” is enabled for a SID, the NDU will signal the brigade for faults and alarms received from that SID.
F3200 Installation & Programming Manual New Zealand Operation 12.8 Document No: LT0122 INSTALLATION : NZ DISPLAY EXTENDER BOARD & BRIGADE DISPLAYS 12.8.1 GENERAL An NDU is not normally used as a brigade connection point. If an NDU is used as a brigade connection point then, in general, a separate display panel must be provided if there needs to be zone alarm indication to the attending Fire Brigade staff.
Document No: LT0122 F3200 Installation & Programming Manual New Zealand Operation MIMIC DISPLAY (CONTINUED) LM0092 PA0483 PA0499 PA0769 PA0753 PA0760 LOOM, CONTROLLER TO FIRST DISPLAY, 1.
F3200 Installation & Programming Manual New Zealand Operation Document No: LT0122 ACTIVE DISPLAY (CONTINUED) FP0678 PA0772 PA0483 LM0056 LM0046 LM0092 16 ZONE FULL STATUS KIT (PA0754,FRC LOOM,POWER LEADS) PFD TERMINATION BOARD (FRC TO MULTICORE) UNPROTECTED TERMINATION BOARD LOOM,DISPLAY EXTENDER FRC,1.4M,26 WAY LOOM, DISPLAY EXTENDER FRC,0.5M,26 WAY LOOM,CONTROLLER TO FIRST DISPLAY,1.
Document No: LT0122 F3200 Installation & Programming Manual New Zealand Operation NDU Cabinet External Mimic Display Cabinet Note: 16 zone display boards are not normally connected to an NDU. Wiring to individual Zone LEDs with series resistors To NDU controller Bd. J13 etc All shaded cables 26 way FRC. The first cable from the NDU Controller must be LM0092 (FZ3031 kit) FIG 12.8.1 - REMOTE PLAN MIMIC DISPLAY Issue 2.
F3200 Installation & Programming Manual New Zealand Operation Document No: LT0122 NDU Cabinet (Special 3 Way cable) 16 Zone Display Board PA0454 (FP0475 including FRC ) Note: 16 zone display boards are not normally connected to an NDU. 16 Zone Display Board PA0454 (FP0475 including FRC Etc. ) To NDU controller Bd. J13 All shaded cables 26 way FRC. The First cable from the NDU controller must be LM0092 (FZ3031 kit). FIG 12.8.
Document No: LT0122 F3200 Installation & Programming Manual New Zealand Operation NDU Cabinet NDU Controller Board Optional 16 Zone Display Boards PA0454 (FP0475) J13 LM0092 PA0772 PFD Term Board 12 Core Shielded Cable (30m Max) Picture Frame Display Cabinet PFD 16 Zone Display Boards PA0741 (alarm only) PA0754 (full status) 26 way FRC Termination Board PA0483 PA0772 PFD Term Board Miscellaneous Inputs Note: This configuration will not generally be used. Refer to Section 12.8.1. FIG 12.8.
F3200 Installation & Programming Manual New Zealand Operation Document No: LT0122 NDU Cabinet PFD Termination Board. PA0772 Links LK1 & LK2 not fitted. J1 From Main Display Boards J3 12 11 10 9 8 7 6 5 4 3 2 1 26 Way FRC C B A J2 Earth 12 Core Shielded Cable Pin1 - Pin 1 : Pin 12 - Pin 12 Picture Frame Display Cabinet (30m max) PFD Termination Board. PA0772 Links LK1 & LK2 fitted. J1 To Display Boards J3 26 Way FRC C B A 12 11 10 9 8 7 6 5 4 3 2 1 J2 Earth FIG 12.8.
Document No: LT0122 F3200 Installation & Programming Manual New Zealand Operation ┌────────────┬─┬─┬─┬─┬───────────────┐ │ └─┴─┴─┴─┘ │ spare 1├─┐ 0 Volt ┌─┤ 16 anc defect 2├─┤ ├─┤ 15 anc fire 3├─┤ 26 way FRC ├─┤ 14 fire led 4├─┤ ┌────────────┐ ├─┤ 13 defect led 5├─┤ └───── ─────┘ ├─┤ 12 normal led 6├─┤ ├─┤ 11 Lamp7├─┤ ├─┤ 10 Lamp+ 8├─┤ ├─┤ 9 ├─┘ +24 Volt └─┤ │ ┌─┬─┬─┬─┐ │ └────────────┴─┴─┴─┴─┴───────────────┘ Outputs Inputs Sprinkler Operated Trial evac Silence alarms Ext defect Lamp test Brigade Isol/
F3200 Installation & Programming Manual New Zealand Operation Document No: LT0122 THIS PAGE INTENTIONALLY LEFT BLANK Page 12-18 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Tandem LCD Mode CHAPTER 13 TANDEM LCD MODE Issue 2.
F3200 Installation & Programming Manual Tandem LCD Mode 13.1 Document No: LT0122 TANDEM LCD MODE Tandem mode allows the LCD and keyboard of an F3200 panel or NDU to be operated from a device on the printer/programmer port or from another device on the network. F3200 or NDU V2.07 or later software allow Tandem LCD mode operation. There are three “modes” of Tandem LCD operation and only one mode may be active at any one time. 1. Local Tandem LCD mode.
Document No: LT0122 F3200 Installation & Programming Manual Appendix A APPENDIX A1 COMPATIBLE ACTUATING DEVICES (DETECTORS) The following detectors are compatible with the F3200 System. The maximum number of detectors per circuit is indicated by the columns 4mA and IS, for Standard and Intrinsically Safe applications. For IS application refer to Section 9.4. ╔═══════════════════════════════════════════════════════╤══════════════╗ ║ DETECTORS COMPATIBLE WITH F3200 FIP │ MAX NO.
F3200 Installation & Programming Manual Appendix A Document No: LT0122 ╔═══════════════════════════════════════════════════════╤══════════════╗ ║ DETECTORS COMPATIBLE WITH F3200 FIP │ MAX NO ║ ╟─────────────┬─────────────────────────────────────────┼───────┬──────╢ ║ TYPE │ DESCRIPTION │ 4mA │ IS ║ ╠═════════════╪═════════════════════════════════════════╪═══════╪══════╣ ║ MD614 │HEAT DETECTOR │ 40 │ - ║ ╟─────────────┼─────────────────────────────────────────┼───────┼──────╢ ║ MF614 │IONISATION SMOKE DETE
Document No: LT0122 F3200 Installation & Programming Manual Appendix A BASES COMPATIBLE WITH DETECTORS DET/ BASE Z51B Z52B Z54B & Z54B MK2 Z55B Z56 C24B & X & X & & C29B & X & X & & C29B Ex X Z56N Z500 Z500 N Z91C & Z94C Z94 & MH2 ' & X P24B & X & X & & P29B & X & X & & T56B & & & & & & & & Table IV Grinnell Detector/Base Range & X ' These detector/base combinations are compatible.
F3200 Installation & Programming Manual Appendix A Document No: LT0122 ╔═══════════════════════════════════════════════════════╤═══════╗ ║ DETECTORS CERTIFIED WITH F3200 FIP │MAX NO.
Document No: LT0122 F3200 Installation & Programming Manual Appendix A ACTUATING DEVICE COMPATIBILITY NOTES 1) The maximum number of detectors per AZC allowed by the standard is 40. 2) Those detectors shown in brackets are old models and have the same characteristics as the current models. 3) Detectors indicated by a "x" may be used in INTRINSICALLY SAFE AREAS in conjunction with approved and compatible, intrinsically safe adaptors.
F3200 Installation & Programming Manual Appendix A Document No: LT0122 APPENDIX A2 PROGRAMMING FOR DETECTOR TYPE 1. GENERAL The default programming (i.e. pre-programmed options) for AZCs (circuits) and zones are shown on the top of the "F3200 INPUT CONFIGURATION" sheet in Appendix B. They are as follows: Circuits ┌──────────┬────────────┬───────────┬─────────────────┬───────────────┐ │ Alarm │ Mode │ Delay │ Voltage Band │ Voltage Band │ │ Text │ │ (Type) │ B1 (0-3V) │ B3 (13-17.
Document No: LT0122 F3200 Installation & Programming Manual Appendix A APPENDIX A2 (CONTINUED) Olsen C23B, C23BEx, R23B, R24B (and Ex where applicable), Flameguard, Intertec, Apollo Series 60. Remote LEDs Where remote LEDs are used, mode 2 may have to be selected to give sufficient current for illumination, depending on the particular LED kit used. Where mode 2 is selected, some detectors require voltage band B3 to be programmed as Alarm. See tables I-V. 4.
F3200 Installation & Programming Manual Appendix A Document No: LT0122 ╔═══════════════════════════════════════════════════════╤══════════════╗ ║ DETECTORS COMPATIBLE WITH F3200 FIP │VOLTAGE BAND ║ ║ │FOR MODES 1&2 ║ ╟─────────────┬─────────────────────────────────────────┼───────┬──────╢ ║ TYPE │DESCRIPTION │MODE 1 │MODE 2║ ╟─────────────┼─────────────────────────────────────────┼───────┼──────╢ ║ MD614 │HEAT DETECTOR │ B2 │ - ║ ╟─────────────┼─────────────────────────────────────────┼───────┼──────╢ ║ M
Document No: LT0122 F3200 Installation & Programming Manual Appendix A ╔══════════════════════════════════════════════════════╤═══════════════╗ ║ DETECTORS CERTIFIED WITH F3200 FIP │VOLTAGE BANDS ║ ║ (SSL # 336) │FOR MODES 1 & 2║ ╟─────────────┬────────────────────────────────────────┼────────┬──────╢ ║ TYPE │ DESCRIPTION │ MODE 1 │MODE 2║ ╠═════════════╪════════════════════════════════════════╪════════╪══════╣ ║ B111B │ BEAM TYPE SMOKE DETECTOR SEE NOTE 1│ B1 │ ║ ╟─────────────┼──────────────────────────
F3200 Installation & Programming Manual Appendix A Document No: LT0122 ╔════════════════════════════════════════════════════╤═════════════════╗ ║ DETECTORS CERTIFIED WITH F3200 FIP │ VOLTAGE BANDS ║ ║ (SSL # 336) │ FOR MODES 1 & 2 ║ ╟─────────────┬──────────────────────────────────────┼────────┬────────╢ ║ TYPE │DESCRIPTION │ MODE 1 │ MODE 2 ║ ╠═════════════╪══════════════════════════════════════╪════════╪════════╣ B3 ║ SERIES 60 │APOLLO HEAT DETECTOR TYPES A, B, C, D │ B2 * │ ║ ╟─────────────┼───────────
Document No: LT0122 F3200 Installation & Programming Manual Appendix B APPENDIX B F3200 CONFIGURATION SHEETS The following pages are suggested as master forms for programming. It is recommended that they be photocopied, and a complete set be filled out for each FIP before programming is started. When programming is complete, the database printout should be checked against the sheets. A copy of the database printout and completed sheets should be kept in the contract file for each installation. Issue 2.
F3200 Installation & Programming Manual Appendix B Document No: LT0122 THIS PAGE INTENTIONALLY BLANK Page B-2 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Appendix B REF:............... F3200/NDU SYSTEM CONFIGURATION PAGE 1 This set of configuration sheets contains all programmable parameters. Fill in values for all parameters that are being changed from the default settings. ................................................................................
F3200 Installation & Programming Manual Appendix B Document No: LT0122 F3200/NDU SYSTEM CONFIGURATION PAGE 2 REF:...............
Document No: LT0122 F3200 Installation & Programming Manual Appendix B F3200/NDU SYSTEM CONFIGURATION PAGE 3 Key REF:...............
F3200 Installation & Programming Manual Appendix B Document No: LT0122 F3200/NDU SYSTEM CONFIGURATION PAGE 4 REF:............... RDU PARAMETERS RZDU protocol Type: LCD RZDU 1 – 8 Text No 1 2 3 4 5 Page B-6 Default Smoke Heat FSW Manual Valve Non-LCD Enabled Y/N Protocol A/B ALARM TEXT NAMES Program Text No Default 6 PSW 7 SPKLR 8 9 5 July 2001 MCP Zone Program Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Appendix B F3200/NDU SYSTEM CONFIGURATION PAGE 5 REF:...............
F3200 Installation & Programming Manual Appendix B Document No: LT0122 F3200 AZC CONFIGURATION REF:............... Number of Zone Modules Fitted …………………. FIELD WIRING AZC PROGRAMMING 8ZM NO. CCT NO.
Document No: LT0122 F3200 Installation & Programming Manual Appendix B F3200/NDU ZONE CONFIGURATION ZONE PROGRAMMING M A F ZONE NO L A T C H A N C 1 A N C 2 B E L L Defaults L M M M M REF:............... ZONE NAME LED ZONE NO. 1 2 3 1 4 5 6 7 8 9 10 11 2 12 13 14 15 16 17 18 19 3 20 21 22 23 24 25 26 27 4 28 29 30 31 32 Issue 2.
F3200 Installation & Programming Manual Appendix B Document No: LT0122 F3200/NDU OPEN COLLECTOR OUTPUT FUNCTION & LOGIC EQUATION REF:............... 8ZM NO. 1 2 3 4 Page B-10 1 OUT PUT 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 1 17 2 18 3 19 4 20 5 21 6 22 7 23 8 24 1 25 2 26 3 27 4 28 5 29 6 30 7 31 8 32 FUNCTION NAME 5 July 2001 LOGIC EQUATION Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Appendix B F3200 RELAY CONFIGURATION 8RM NO. RLY NO. DEFAULTS 1 2 3 4 1 2 1 2 3 3 4 5 4 5 6 7 6 7 8 8 1 2 9 10 3 11 4 5 12 13 6 14 7 8 15 16 1 17 2 3 18 19 4 20 5 6 21 22 7 23 8 1 24 25 2 26 3 4 27 28 5 29 6 7 30 31 8 32 Issue 2.7 REF:...............
F3200 Installation & Programming Manual Appendix B Document No: LT0122 F3200/NDU RELAY FUNCTIONS & LOGIC EQUATIONS REF:............... 8RM NO. 1 2 3 4 Page B-12 1 RELAY NO. 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 1 17 2 18 3 19 4 20 5 21 6 22 7 23 8 24 1 25 2 26 3 27 4 28 5 29 6 30 7 31 8 32 NAME LOGIC EQUATION 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Appendix B F3200 RELAY FIELD WIRING REF:............... Number of 8RMs:............... 8RM NO. 1 2 3 4 Issue 2.7 RELAY NO.
F3200 Installation & Programming Manual Appendix B F3200/NDU ZONE DISPLAY BOARD LED CONTROL LOGICAL RELAY NO (65-256) Page B-14 LED SET (1-64) Document No: LT0122 REF:............... PAGE..... of ...... ALARM, FAULT, ISOLATE LOGIC EQUATION 5 July 2001 Issue 2.
Document No: LT0122 F3200 Installation & Programming Manual Appendix B F3200/NDU TIMERS, VARIABLES, NETWORK VARIABLES & ZONE ISOLATE/ DEISOLATE/RESET EQUATIONS TIMER/VARIABLE/ NETVARS/ZONE CMD/SNA Issue 2.7 REF:...............
F3200 Installation & Programming Manual Appendix B Document No: LT0122 F3200/NDU CONFIGURATION SHEETS REF:............... NETWORK PARAMETERS FILL IN VALUES FOR ALL PARAMETERS THAT ARE BEING CHANGED FROM DEFAULT.
Document No: LT0122 F3200 Installation & Programming Manual Appendix B F3200/NDU CONFIGURATION NETWORK SID LIST CONFIGURATION SID NO. 1-254 Issue 2.7 LINK RX Y/N LOG EVNT Y/N RX FFCIF Y/N TX CMD Y/N 5 July 2001 REF:...............
F3200 Installation & Programming Manual Appendix B Document No: LT0122 THIS PAGE INTENTIONALLY LEFT BLANK Page B-18 5 July 2001 Issue 2.