Technical data

5.2.2. Grid Impedance
The grid impedance must correspond to the specifications to avoid unintended disconnection
from the grid or derating of the output power. It is similarly important that proper cable dimen-
sions are used to avoid losses. Additionally the no load voltage at the connection point must be
taken into account. The maximum permitted grid impedance, as function of no load voltage for
the TripleLynx CN inverter series, can be found in the following graph.
Illustration 5.5: Grid impedance: Maximum permissible grid impedance [] versus No load grid voltage [V]
5. Requirements for Connection
28 L00410582-01_02
5