Programming instructions

86
Information
Name Address
Building Type
Setting ACT 1 ACT 2 Description
Actuator jam alarm Yes No Yes No
Select Ventilation displays and alarm message when it
detects an actuator jam.
Minimum set point
The actuator will close completely when the temperature is
below this value.
Minimum position
The actuator is at this position when the temperature is
between the minimum and stage 1 set points.
Stage 1 set point
When the temperature is at this value, the actuator starts
opening for stage 1.
Stage 1 differential
When the temperature is at this value, the actuator is at the
stage 1 position.
Stage 1 position
When the temperature is at the differential value, the
actuator is at this position.
Stage 2 set point
When the temperature is at this value, the actuator starts
opening for stage 2.
Stage 2 differential
When the temperature is at this value, the actuator is at the
stage 2 position.
Stage 2 position
When the temperature is at the differential value, the
actuator is at this position.
Stage 3 set point
When the temperature is at this value, the actuator starts
opening for stage 3.
Stage 3 differential
When the temperature is at this value, the actuator is at the
stage 3 position.
Stage 3 position
When the temperature is at the differential value, the
actuator is at this position.
Stage 4 set point
When the temperature is at this value, the actuator starts
opening for stage 4.
Stage 4 differential
When the temperature is at this value, the actuator is at the
stage 4 position.
Stage 4 position
When the temperature is at the differential value, the
actuator is at this position.
Temperature in °F/°C, range: 14.0 to 122.0°F, –10.0 to 50.0°C
Position in %, range: 0 to 100 %