Programming instructions

Programming equipment settings
57
Notes about duty cycles
Duty cycles always start with the ON duration.
When Power Blocks restart after a power failure, duty cycles restart with the ON duration. If the
duty cycles resetting could cause a problem at your site, timed events are another option to
consider. For more information, read Programming timed events on page 59.
The minimum ON or OFF duration is 5 seconds (0:00:05 hours:minutes:seconds).
The maximum ON or OFF duration is 5 hours (5:00:00 hours:minutes:seconds)
When there is a change to the settings:
PBx Power Blocks immediately switch to the ON duration as soon as the Power Block receives
the settings change.
PB-1 to PB-5 Power Blocks must complete their current ON or OFF duration before any
settings changes will take effect. For example, if you have a five-hour duty cycle that just started
an ON or OFF duration and you change it to a ten-minute duty cycle, you will have to wait for
the five-hour duration to complete before the new settings will take effect.
The Ventilation settings window is where you program single-stage heating and cooling relays.
A This button displays the relay settings.
B This is where you select the relay you want to program.