MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 10 of 70
Form 1003
1.3.2 Read input register
Command code: 0x04
This command is used to read out the content from multiple input registers.
Input registers are parameters for which only read access is possible.
Command from master:
4 data bytes are transmitted:
1st MSB input register address
1st LSB input register address
Number of MSB addresses to be read
Number of LSB addresses to be read
The input registers are described below.
Response from fan:
The following data bytes are transmitted:
Byte count (number of addresses to be read * 2)
Data in 1st MSB holding register
Data in 1st LSB holding register
Optional:
Data from the following input registers (0 to n)
Exception codes:
In case of error, only one data byte (the exception code) will be transmitted
Exception codes:
0x02: Permissible range of the input registers 0xD000 to 0xD0FF exceeded
0x03: Maximum telegram length for response (23 bytes) exceeded,
i.e. either more than 9 input registers or 0 input registers were requested.