MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 11 of 70
Form 1003
1.3.3 Write single register
Command code: 0x06
This command is used to write the content of one holding register.
Command from master:
4 data bytes are transmitted:
MSB holding register address
LSB holding register address
MSB data to be written
LSB data to be written
The holding registers are described below.
Response from fan:
4 data bytes are transmitted:
MSB holding register address
LSB holding register address
MSB data to be written
LSB data to be written
Exception codes:
In case of error, only one data byte (the exception code) will be transmitted
Exception codes:
0x02: Permissible range of the holding registers 0xD000 to 0xD3FF exceeded
0x04: There is no write access in this authorisation level (password).